ControlWave Express Instruction Manual (CI-ControlWave Express)
3.3.6 Non-Isolated High Speed Counter (HSC) / Discrete Inputs (DI)
on TB4 of Process I/O Board
Process I/O Board connector TB4 provides interface to two internally
sourced single-ended high speed counter/discrete inputs (HSC1 and
HSC2).
Table 3-8. Non-Isolated High Speed Counter/Discrete Inputs General
Characteristics
Type Number
Supported
Characteristics
High Speed
Counter /
Discrete Inputs
2 on TB4
of Process
I/O board
Surge suppression
and signal
conditioning.
HSCs can use dry contacts or open
collector field circuits.
High speed counter switch-selectable
frequency of 10kHz or 300Hz.
Sourced from 3.3Vdc and switch
selectable for a source current of
200
μ
A (switch SW1-3 = OFF) or
2.2mA (switch SW1-3 = ON).
Note:
These switches affect all DIs and
HSCs.
Wiring
See
Figure 3-2
for wiring diagrams.
Switch Settings
See
Table 2-1
for details on setting switches.
Software Configuration
To use data from these high speed counter/discrete inputs you must
include a
CWM_EIO
board in your ControlWave project using
ControlWave Designer’s I/O Configurator, and then configure it. See
the
ControlWave Designer Programmer's Handbook
(D5125) for more
information. That same manual includes an
I/O Mapping
section that
describes, for advanced users, the I/O map for this board. To read a DI
value, look at the appropriate offset for the _STATE variable for the
board.
Revised Mar-2011
I/O Configuration and Wiring
3-11
Summary of Contents for Bristol ControlWave Express
Page 4: ...This page is intentionally left blank ...
Page 38: ...This page is intentionally left blank ...
Page 54: ...This page is intentionally left blank ...
Page 78: ...This page is intentionally left blank ...
Page 82: ...This page is intentionally left blank ...