![Emerson Bristol ControlWave Express Instruction Manual Download Page 31](http://html.mh-extra.com/html/emerson/bristol-controlwave-express/bristol-controlwave-express_instruction-manual_101199031.webp)
ControlWave Express Instruction Manual (CI-ControlWave Express)
Full-duplex
Cable
(PPP Protocol)
Half-dup
Cable
9-Pin Female
“D” Connector
J4 (COM1)
{
9-Pin Female
“D” Connector
J4 (COM1)
{
lex
CW Express
TB3 (COM2)
CW Express
TB3 (COM2)
3305/3310/3330/3335/CW_10/30/35
3305/3310/3330/3335/CW_10/30/35
9-Pin Male
“D” Connector
P1
2 = TXD
6 = CTS
7 = DCD
5 = RTS
4 = RXD
1 = DTR
9 = GND
To P2 Pin-2
To P2 Pin-3
To P2 Pin-5
3 = TXD
2 = RXD
5 = GND
P2
7 = RTS
8 = CTS
4 = DTR
1 = DCD
9-Pin Male
“D” Connector
P1
9= GND
7 = DCD
6 = CTS
4 = RXD
2 = TXD
1 = DTR
5 = RTS
To P2 Pin-5
To P2 Pin-4
To P2 Pin-3
To P2 Pin-2
To P2 Pin-1
3 = TXD
7 = RTS
8 = CTS
4 = DTR
2 = RXD
1 = DCD
5 = GND
P2
P2
P2
3 = TXD
7 = RTS
8 = CTS
4 = DTR
2 = RXD
1 = DCD
5 = GND
1
2
3
4
5
6
7
8
or
3 = TXD
6 = DSR
7 = RTS
4 = DTR
2 = RXD
1 = DCD
5 = GND
8 = CTS
1
2
3
4
5
6
7
8
Figure 2-7. Full-duplex and Half-duplex Cable
Refer to
Figure 2-8
when using COM2 of the ControlWave Express to
connect with an external modem or external radio.
PL Modem
or Radio
Intf.
Cable
PSTN Modem
Intf.
Cable
To TXD
To RXD
To DCD
To DTR
To GND
TB3
(COM2)
To/From
MODEM
3 = TXD
7 = RTS
8 = CTS
4 = DTR
2 = RXD
1 = DCD
5 = GND
1
2
3
4
5
6
7
8
3 = TXD
6 = DSR
7 = RTS
8 = CTS
4 = DTR
2 = RXD
1 = DCD
5 = GND
1
2
3
4
5
6
7
8
To TXD
To RXD
To RTS
To CTS
To GND
To/From
RADIO
Figure 2-8. Connection from an External Modem/Radio to COM2 of the
ControlWave Express
Revised Mar-2011
Installation
2-17
Summary of Contents for Bristol ControlWave Express
Page 4: ...This page is intentionally left blank ...
Page 38: ...This page is intentionally left blank ...
Page 54: ...This page is intentionally left blank ...
Page 78: ...This page is intentionally left blank ...
Page 82: ...This page is intentionally left blank ...