background image

Product Data Document

420ds9b

July 10, 2007 - Page 2

ControlWave Upgrade Kits

www.EmersonProcess.com/Remote

Remote Automation Solutions

Permit access to onboard FLASH RAM (33XX 

has FLASH for boot project only) 
Optional one or two 10/100 Mbit Ethernet ports 
CW_10 MFIB with four serial ports
CW_30 with two BIP serial ports
CW_35 with two serial ports
CW_31 with one Ethernet port
New Communication card or 3310 MFIB for high 

speed ports & IP/PPP serial communication 
CPU speed increase of up to 1000% 
New Protocols – DNP3.0 & CIP 

Software Migration 

In order to preserve most of your ACCOL program 

development time and expense, the ACCOL Trans-

lator utility will allow application program conversion 

to ControlWave Designer IEC 1131 Structured Text. 

For most applications, the ACCOL Translator will 

reduce the conversion effort by up to 80% vs. rewrit-

ing the program. 

To properly take advantage of the ACCOL Transla-

tor, one must know ACCOL, ControlWave Designer, 

understand the ACCOL application and have access 

to the ACCOL source file. Once the application is 

translated, it typically requires some degree of edit-

ing, depending on the complexity of the program, 

and thorough testing prior to deployment on-site. 

Emerson Process Management can provide you 

with training to do the translation or you can rely on 

our Application Support Group to do the translation 

for you.

Specifications

CW_10, CW_30, and CW_35 CPU 

32 bit, 150 MHz ARM processor 
Memory battery backup: 7000 hours 
Optional one or two independent 10/100 Base-

T ports with RJ-45 connectors (CW_30 and 

CW_35 only) 









Ethernet port isolation: 500 Vdc 
One 3 pin Utility Port for Flash downloading 

system flashware 

System Watchdog relay on CW_10 MFIB 
LED status indicators – 6 failure status LEDs, 

Watchdog and Idle and communication LEDs 

Memory

Program execution: 4 MB SD RAM 
Data Memory : 1 MB SRAM battery backed 

memory 
File and Historical Archive memory: 16 MB on-

board flash 

CW_10 Serial Communication Ports

4 Serial communication ports: Located on the 

MFIB: 9 pin ‘D’ connectors with standard 33XX 

pin out
Ports A & C: RS232 – 115.2 K baud 

Port B: Configurable Modem/RS485 – 115.2 

K baud. Supports all existing 3310 private and 

switched network modems 
Port D: RS485 – 115.2 K baud, multi-drop up to 

32 nodes 
ESD protection on RS 485 ports - IEC 801 

CW_30 and CW_35 Serial Communication Ports

2 Serial communication ports: BIP ports.  (On 

CW_30 only BIP ports extended from CPU 

board and mounted on an external bracket)

BIP ports are configurable RS232/RS485 

– 115.2 K baud
BIP ports are 9 pin ‘D’ connectors with standard 

33XX pin out 
ESD protection on RS 485 ports - IEC 801

CW_30 and CW_35 Serial Communication Card 

2 port and 4 port serial communication cards 

available 





Summary of Contents for Bristol ControlWave CW_10

Page 1: ...monly used analog discrete and counter I O cards as well as modems and radios currently installed in the RTUs Communication compatibility is maintained through the same use of BSAP and Modbus proto cols as were used in the 33XX Benefits The ControlWave architecture offers several ad vantages over existing 3310 3330 3335s including increased compatibility with industry standards such as IEC 61131 3...

Page 2: ...with training to do the translation or you can rely on our Application Support Group to do the translation for you Specifications CW_10 CW_30 and CW_35 CPU 32 bit 150 MHz ARM processor Memory battery backup 7000 hours Optional one or two independent 10 100 Base T ports with RJ 45 connectors CW_30 and CW_35 only Ethernet port isolation 500 Vdc One 3 pin Utility Port for Flash downloading system fla...

Page 3: ...50Hz to 2000Hz RFI Susceptibility 3V m 80 MHz to 1000Mhz EN50082 2 Power Consumption CPU without Ethernet 2 watt CPU with 1 Ethernet 3 watt CPU with 2 Ethernet 4 watt MFIB Watchdog off 1 watt MFIB Watchdog on 1 9 watt CW_XX 2 port comm 0 5 watt CW_XX 4 port comm 1 watt Hazardous Area Approvals FM approved as non incendive for operation in Class I Division 2 hazardous areas Ordering Information 331...

Page 4: ...lity RAS reserves the right to modify or improve the designs or specifications of such products at any time without notice All sales are governed by RAS terms and conditions which are available upon request RAS does not assume responsibility for the selection use or maintenance of any product Responsibility for proper selection use and maintenance of any RAS product remains solely with the purchas...

Reviews: