Actuator Configuration
Section 6: Actuator Configuration
Figure 14
Removal of the control unit cover
6.2
Local Configuration of the SCE300
CAUTION
Actuator configuration must be done while actuator is powered on. Do not touch any
components not required for configuration to avoid injury or damage to equipment.
WARNING
Installation, configuration, commissioning, maintenance, and repairs must be performed
by approved and qualified personnel only.
6.2.1
SCE300 Default General Configuration
The actuator is set in the factory to the following default configuration:
•
CLOSE (CL) Limit Relay by position
•
OPEN (OP) Limit relay by position
•
Stroking time in CL (6): 28 s for models 063/125/250/500, 45 s for model 1000
and 100 s for model 2000
•
Stroking time in OP (6): 28 s for models 063/125/250/500, 45 s for model 1000
and 100 s for model 2000
•
Torque limiting device in CL set at about 100% of nominal torque
•
Torque limiting device in OP set at about 100% of nominal torque
•
Reverse mode off
•
Monitor Relay NC (in normal condition, i.e. without alarms)
•
Blinker / Local Selector relay off (always Open)
If the application requires a different actuator configuration(s), proceed as described in
this Section.