Installation, Operation and Maintenance Manual
VCIOM-15746-EN Rev. 0
June 2021
Installation
7
Section 3: Installation
Connect both ribbon cable and 8-pole connector with the logic board, after install the
logic + relay board back to the control (two small screws for original installation will
remain). Take care of possible damage of cables or other parts.
Figure 11
Connect cable between display cover and logic board. Perform a Firmware update before
installing display cover on the unit. This update is important for the following programming
steps (use FW version display 1507, logic 219 or higher). For a detailed description on how
to preform a firmware update, please refer to separate manual.
During display cover installation, pay attention to the O-ring which must sit correct
between cover and housing and fix it with the 4 hexagon socket screws.
Figure 12