6 Basic parameters
Menu 0 is used to bring together various commonly used parameters for basic easy set up of the drive. All the parameters in menu 0 appear in other
menus in the drive (denoted by {…}).
Menus 11 and 22 can be used to change most of the parameters in menu 0. Menu 0 can also contain up to 59 parameters by setting up menu 22.
6.1 Single line descriptions
Table 6-1 Single line descriptions
Parameter
Range(
Ú
)
Default(
Ö
)
OL
RFC
OL
RFC
0.00
xx.00
{
x.00
}
0 to 32,767
0
0.01
Minimum reference clamp
{
1.07
}
±3,000.0Hz
±SPEED_LIMIT_
MAX Hz/rpm
0.0
0.02
Maximum reference clamp
{
1.06
}
0 to 3,000.0Hz
SPEED_LIMIT_
MAX Hz/rpm
EUR> 50.0
USA> 60.0
EUR> 1,500.0
USA> 1800.0
0.03
Acceleration rate
{
2.11
}
0.0 to 3,200.0
s/100Hz
0.000 to 3,200.000
s/1,000rpm
EUR> 40.0
USA> 33.3
EUR> 13.333
USA> 11.111
0.04
Deceleration rate
{
2.21
}
0.0 to 3,200.0
s/100Hz
0.000 to 3,200.000
s/1,000rpm
EUR> 40.0
USA> 33.3
EUR> 13.333
USA> 11.111
0.05
Reference select
{
1.14
}
A1.A2 (0), A1.Pr (1), A2.Pr (2), Pr (3), PAd (4), Prc (5)
A1.A2 (0)
0.06
Current limit
{
4.07
}
0 to CURRENT_LIMIT_MAX %
110
0.07
OL> Voltage mode select
{
5.14
}
Ur_S (0),
Ur (1), Fd (2), Ur_Auto (3),
Ur_I (4), SrE (5)
Fd (2)
RFC> Speed controller P gain
{
3.10
}
0.0000 to 6.5535
1/rad s
-1
0.0300
0.08
OL> Voltage boost
{
5.15
}
0.0 to 25.0% of motor
rated voltage
Size 1 to 3: 3.0
Size 4 & 5: 2.0
Size 6: 1.0
RFC> Speed controller I gain
{
3.11
}
0.00 to 655.35 1/rad
0.10
0.09
OL> Dynamic V/F
{
5.13
}
OFF (0) or On (1)
OFF (0)
RFC> Speed controller D gain
{
3.12
}
0.00000 to
0.65535 (s)
0.00000
0.10
OL> Estimated motor speed
{
5.04
}
±180,000 rpm
RFC> Motor speed
{
3.02
}
±SPEED_MAX rpm
0.11
Drive output frequency
{
5.01
}
±SPEED_FREQ_MAX Hz
±1250 Hz
0.12
Total motor current
{
4.01
}
0 to DRIVE_CURRENT_MAX A
0.13
Percentage load
{
4.20
}
±USER_CURRENT_MAX %
0.14
Ramp mode select
{
2.04
}
FASt (0)
Std (1)
Std.hV (2)
FASt (0)
Std (1)
Std (1)
0.15
Sleep/wake threshold
{
6.53
}
±SPEED_FREQ_MAX Hz/rpm
0.0
0.16
Sleep/wake delay time
{
6.54
}
0.0 to 250.0 s
10.0
0.17
RFC> Current demand filter 1
{
4.12
}
0.0 to 25.0 ms
0.0
0.18
Spin start boost
{
5.40
}
0.0 to 10.0
1.0
0.19
Analog input 2 mode
{
7.11
}
0-20 (0), 20-0 (1), 4-20tr (2), 20-4tr (3),
4-20 (4), 20-4 (5), VOLt (6)
4-20 (4)
0.20
Analog input 2 destination
{
7.14
}
Pr
0.00
to Pr
50.99
Pr
1.37
0.21
Analog input 3 mode
{
7.15
}
0-20 (0), 20-0 (1), 4-20tr (2), 20-4tr (3),
4-20 (4), 20-4 (5), VOLt (6), th.SC (7),
th (8), th.diSp (9)
VOLt (6)
0.22
Date
{
6.16
}
0 to 311299
0.23
Time
{
6.17
}
0.00 to 23.59
0.24
Date/Time selector
{
6.19
}
0 to 5
3
0.25
Date format
{
6.20
}
Std (0), Std.ds (1), US (2), US.ds (3)
EUR> Std (0), USA> US (2)
0.26
Low load detection level
{
4.27
}
0.0 to 100.0 %
0.0
0.27
Low load detection speed / frequency
threshold
{
4.28
}
0.0 to +SPEED_FREQ_MAX Hz/rpm
0.0
0.28
Trip on abnormal load detection
{
4.29
}
OFF (0) or On (1)
OFF (0)
0.29
SMARTCARD parameter data
{
11.36
}
0 to 999
0
0.30
Parameter cloning
{
11.42
}
nonE (0), rEAd (1), Prog (2), AutO (3), boot (4)
nonE (0)
0.31
Drive rated voltage
{
11.33
}
200 (0), 400 (1), 575 (2), 690 (3) V
0.32
Drive current scaling
{
11.32
}
0.00 to 9999.99A
0.33
Catch a spinning motor
{
6.09
}
0 to 3
0 to 1
0
1
0.34
User security code
{
11.30
}
0 to 999
0
0.35
PC comms mode
{
11.24
}
AnSI (0), rtU (1), Lcd (2)
rtU (1)
0.36
PC comms baud rate
{
11.25
}
300 (0), 600 (1), 1200 (2), 2400 (3),
4800 (4), 9600 (5), 19200 (6), 38400 (7),
57600 (8) Modbus RTU only,
115200 (9) Modbus RTU only
19200 (6)
0.37
PC comms address
{
11.23
}
0 to 247
1
0.38
Hold zero speed / Motor pre-heat enable
{
6.08
}
OFF (0) or On (1)
OFF (0)
Summary of Contents for Affinity