FEATURES_SEL
FEATURES_SEL is used to turn on any of the supported features. The default
setting of the Rosemount 8742C does not select any of these features.
Choose one of the supported features if any.
MAX_NOTIFY
The MAX_NOTIFY parameter value is the maximum number of alert reports
that the resource can have sent without getting a confirmation, corresponding
to the amount of buffer space available for alert messages. The number can
be set lower, to control alert flooding, by adjusting the LIM_NOTIFY
parameter value. If LIM_NOTIFY is set to zero, then no alerts are reported.
PlantWeb
™
Alarms
The Resource Block will act as a coordinator for PlantWeb alarms.
There will be three alarm parameters (FAILED_ALARM,
MAINT_ALARM, and ADVISE_ALARM) which will contain
information regarding some of the device errors which are
detected by the transmitter software. There will be a
RECOMMENDED_ACTION parameter which will be used to
display the recommended action text for the highest priority alarm.
FAILED_ALARM will have the highest priority followed by MAINT_ALARM
and ADVISE_ALARM will be the lowest priority.
FAILED_ALARMS
A failure alarm indicates a failure within a device that will make the device or
some part of the device non-operational. This implies that the device is in
need of repair and must be fixed immediately. There are five parameters
associated with FAILED_ALARMS specifically, they are described below.
FAILED_ENABLED
This parameter contains a list of failures in the device which makes the
device non-operational that will cause an alarm to be sent. Below is a list
of the failures with the highest priority first.
1.
Output Board Electronics Failure
2.
Sensor Board Electronics Failure
3.
Output Board NV Memory Failure
4.
Coil Drive Open Circuit Failure
Table 4-1. WRITE_LOCK Parameter
FEATURE_SEL
HW_SEL bit
FEATURE_SEL
SW_SEL bit
SECURITY SWITCH
WRITE_LOCK
WRITE_LOCK
Read/Write
DEFINE_WRITE_LOCK
Write access
to blocks
0 (off)
0 (off)
NA
1 (unlocked)
Read only
NA
All
0 (off)
1 (on)
NA
1 (unlocked)
Read/Write
NA
All
0 (off)
1 (on)
NA
2 (locked)
Read/Write
Physical
Function
Blocks only
0 (off)
1 (on)
NA
2 (locked)
Read/Write
Everything
None
1 (on)
0 (off)
(1)
0 (unlocked)
1 (unlocked)
Read only
NA
All
1 (on)
0 (off)
1 (locked)
2 (locked)
Read only
Physical
Function
Blocks only
1 (on)
0 (off)
1 (locked)
2 (locked)
Read only
Everything
None
(1) The hardware and software write lock select bits are mutually exclusive and the hardware select has the highest priority. When the HW_SEL bit if set to 1
(on), the SW_SEL bit is automatically set to 0 (off) and is read only.
Summary of Contents for 8700 Series
Page 2: ......
Page 4: ......
Page 12: ...Reference Manual 00809 0100 4793 Rev CA August 2004 1 4 Rosemount 8742C ...
Page 64: ...Reference Manual 00809 0100 4793 Rev CA August 2004 5 12 Rosemount 8742C ...
Page 102: ...Reference Manual 00809 0100 4793 Rev CA August 2004 Rosemount 8742C A 32 ...
Page 116: ...Reference Manual 00809 0100 4793 Rev CA August 2004 Rosemount 8742C B 14 ...
Page 135: ......