[46]
Figure 29.
Replacing a Battery Disconnect Contactor in a 1-Row Distribution Cabinet
Battery
Disconnect
Contactor
Apply electrical anti-oxidizing
compound to busbar mating surfaces.
Components removed in
illustration for clarity only.
Contactor styles vary
between manufacturer’s.
Front
5/16-18 x 1” Bolt
5/16" Belleville Lock Washer
5/16" Belleville Lock Washer
(concave side of Belleville
Lock Washers face each other)
5/16" Hardened Flat Washer
(4 places)
Torque to 100 in-lbs.
White/Black Wire
Brown Wire
Brown/White Wire
Red/White Wire
Brown Wire
Brown/White Wire
White/Black Wire
Red/White Wire