![Emerson 582127000 User Instructions Download Page 48](http://html.mh-extra.com/html/emerson/582127000/582127000_user-instructions_103989048.webp)
NetSure
™
-48V DC Power System
User Instructions, UM582127000 (Issue AD, January 20, 2014)
Spec. No: 582127000
Code: UM582127000
Model No: 721
NPBB
Issue AD, January 20, 2014
[40]
Figure 25.
Optional LVD Driver Circuit Card Connector Locations
J1, J2, J3
To LVLD contactor, uses ACU+
LVD1 control setting (Level 1).
J4, J5, J6
To LVLD contactor, uses ACU+
LVD2 control setting (Level 2).
J7
To LVBD contactor, uses ACU+
LVD2 control setting (Level 2).
Notes:
1. Connects up to (4) LVLD
and (1) LVBD contactors.
2. Switch and indicator located
on circuit card installed in
Main Bay only.
J6
J5
J4
J3
J2
J1
J7
S1
DO NOT change a Low Voltage
Load Disconnect contactor to
LVD Control Level 2 (LVD2) if
the system is furnished with a
Low Voltage Battery Disconnect
contactor.