IM581127000
Installation Instructions
Issue AB, March 22, 2012
Spec. No. 581127000 (Model 710
NPBA
)
Page 66
Chapter 4. Making Electrical Connections
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
LOAD CONNECTIONS
Loads are connected to the various distribution panels located inside the distribution
cabinet, as detailed in this section.
Recommended Torques
72 in-lbs for 1/4-inch hardware (when using standard flat and lock washer).
300 in-lbs for 3/8-inch hardware (when using standard flat and lock washer).