Chapter 5. Installing the Modules and Initially Starting the System
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
8)
Without readjusting the “24V Under Volt1” setpoint, press the
ESC
key
repeatedly to return to the Main Menu. Then navigate as follows:
Settings
(ENT)
/
“
Power System
” (ENT) / “
General
” (ENT)
/
“
24V Under Volt2
”. Record the
displayed voltage setpoint.
9) Press
ENT
. Use the up or down arrow
keys to adjust the “24V Under Volt2”
value to one-half volt above the system voltage recorded in step 3). Press
ENT
.
a) Requirement:
An audible alarm sounds. Alarm will be silenced in
Requirement c).
b) Requirement:
ACU+ “Critical/Major” alarm indicator stays red.
c) Requirement:
Press
ESC
repeatedly to return to the Main screen. ACU+
displays “
Alarm
”.
To see the specific alarm, press
ENT
to display the Main Menu.
Navigate as follows: “
Status
” (ENT) / “
Active Alarm
” (ENT).
The Active Alarm screen lists two critical alarm.
Press
ENT
.
“
Power System 24V Under Volt2 Critical
” is displayed.
Use arrow keys to scroll through the list of alarms.
“
Power System 24V Under Volt1 Critical
” is displayed.
d) Requirement:
External
“Relay 1 Critical Summary Alarm” and “Relay 4
Under Voltage 1 Alarm
” remain active. External “Relay 5 Under Voltage 2
Alarm
” activates.
10) Press
ESC
repeatedly to return to the Main Menu. Navigate to “
Settings
” (ENT)
/ “
Power System
” (ENT) / “
General
” (ENT) / “
24V Under Volt2
”.
11) Press
ENT
. Use the up or down arrow
keys to adjust the “24V Under Volt2”
setting to the value recorded in step 8). Press
ENT
.
12) Use the up or down arrow
keys to scroll up to “
24V Under Volt1
”.
13) Press
ENT
. Use the up or down arrow
keys to adjust the “24V Under Volt1”
setting to the value recorded in step 6). Press
ENT
.
a) Requirement:
ACU+ “Critical/Major” alarm indicator goes from red to off.
b) Requirement:
Press
ESC
repeatedly to return to the Main screen. ACU+
displays “
No Alm
”.
c) Requirement:
All external alarms deactivate.
Checking System Over Voltage Alarm 1 and Over Voltage Alarm 2 Procedure
1) Verify system is operating and no alarms are present.
2) Verify the ACU+ displays the Main screen. If not, press
ESC
repeatedly to return
to the Main screen.
3) Record the system voltage displayed on the ACU+ Main screen.
4) Press
ENT
to go to the Main Menu. Navigate to and select
“
Settings
” (ENT).
5) If a password screen opens, a password must be entered to allow the User to
make adjustments. If a password was previously entered and has not yet timed
out, skip this step and proceed to step 3). Otherwise, to enter a password, with
the cursor at the User Name field
(default is “Admin”), press the down arrow key
to move cursor down to the password line. Press
ENT
. “0” is highlighted. Press
the
up arrow key once to change the “0” to”1” (default password is “1”), then
press
ENT
twice.
(
Note:
If you have been assigned a unique User Name and
password, follow this procedure to enter these.)