![Emerson 2202 Advanced User'S Manual Download Page 38](http://html.mh-extra.com/html/emerson/2202/2202_advanced-users-manual_101992038.webp)
Menu 1
38
Commander SK Advanced User Guide
www.controltechniques.com Issue Number: 9
Indication of the reference being used by the drive for system setup and fault finding.
Indication of the reference being used by the drive for system setup and fault finding.
Reference used for jogging. See section 10.7
Menu 6: Drive sequencer and clock
for details on when the jog mode can be activated.
This parameter is a symmetrical limit on both directions of rotation.
Defines drive absolute maximum frequency reference. Slip compensation and current limit can increase the motor frequency further.
1.01
Frequency reference selected {81}
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
1
1
1
1
1
Range
±550 Hz
Update rate
5ms
1.02
Pre-skip filter reference {82}
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
1
1
1
1
1
Range
±550 Hz
Update rate
5ms
1.03
Pre-ramp reference {83}
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
1
1
1
1
1
Range
±550 Hz
Update rate
5ms
1.04
Reference offset
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
1
1
1
1
Range
±550 Hz
Default
0.0
Update rate
5ms
1.05
Jog reference {15}
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
1
1
1
1
Range
0.0 to 400.0 Hz
Default
1.5
Update rate
5ms
1.06
Maximum set speed {02}
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
1
1
1
1
Range
0.0 to 550 Hz
Default
Eur: 50.0
USA: 60.0
Second motor
parameter
Pr
Update rate
Background