Commander SK Advanced User Guide
www.controltechniques.com Issue Number: 9
10.7 Menu 6: Drive sequencer and clock
Table 10-8 Menu 6 parameters: single line descriptions
* Only available on Commander SK size B, C and D.
** On with USA defaults.
Parameter
Range
Default
Setting
Update Rate
6.01
Stop mode select
{
31
}
0 to 4
1
2 ms
6.02
Not used
6.03
Mains loss mode
diS(0), StoP(1), rd.th(2)
diS(0)
2 ms
6.04
Start/stop logic select
{
11
}
0 to 6
0 (Eur)
4 (USA)
Edit mode exit
6.05
Not used
6.06
Injection braking level
0.0 to 150.0%
100.0
B
6.07
Injection braking time
0.0 to 25.0 s
1.0
2 ms
6.08
Not used
6.09
Catch a spinning motor select
{
33
}
0 to 3
0
B
6.10
Low DC bus operation*
OFF(0) or On(1)
OFF(0)
B
6.11
Remote LED keypad function key status
OFF(0) or On(1)
OFF(0)
B
6.12
Enable stop key
OFF(0) or On(1)
OFF(0)**
B
6.13
Function key mode
0 to 6
0
BR
6.14
Disable auto reset on enable
OFF(0) or On(1)
OFF(1)
2 ms
6.15
Drive enable
OFF(0) or On(1)
On(1)
2 ms
6.16
Electricity cost per kWh
0.0 to 600.0 currency/kWh
0.0
B
6.17
Reset energy meter
OFF(0) or On(1)
OFF(0)
B
6.18
Not used
6.19
Not used
6.20
Not used
6.21
Not used
6.22
Run time log: years.days
0.000 to 9.365 years.days
B
6.23
Run time log: hours.minutes
0.00 to 23.59 hours.minutes
B
6.24
Energy meter: MWh
0.0 to 999.9 MWh
B
6.25
Energy meter: kWh
0.00 to 99.99 kWh
B
6.26
Running cost
±
32000 currency/hour
B
6.27
Not used
6.28
Not used
6.29
Hardware enable
OFF(0) or On(1)
OFF(0)
2 ms
6.30
Sequencing bit: Run forward
OFF(0) or On(1)
OFF(0)
2 ms
6.31
Sequencing bit: Jog forward
OFF(0) or On(1)
OFF(0)
2 ms
6.32
Sequencing bit: Run reverse
OFF(0) or On(1)
OFF(0)
2 ms
6.33
Sequencing bit: Fwd/Rev
OFF(0) or On(1)
OFF(0)
2 ms
6.34
Sequencing bit: Run
OFF(0) or On(1)
OFF(0)
2 ms
6.35
Forward limit switch
OFF(0) or On(1)
OFF(0)
2 ms
6.36
Reverse limit switch
OFF(0) or On(1)
OFF(0)
2 ms
6.37
Sequencing bit: Jog reverse
OFF(0) or On(1)
OFF(0)
2 ms
6.38
Not used
6.39
Sequencing bit: /Stop
OFF(0) or On(1)
OFF(0)
2 ms
6.40
Enable sequencer latching
OFF(0) or On(1)
OFF(0)
2 ms
6.41
Not used
6.42
Control word
0 to 32767
0
2 ms
6.43
Control word enable
OFF(0) or On(1)
OFF(0)
2 ms
6.44
Not used
6.45
Force cooling fan to run at full speed
OFF(0) or On(1)
OFF(0)
B