Menu 11
Commander SK Advanced User Guide
147
Issue Number: 9 www.controltechniques.com
If any number, other than 0 is programmed into this parameter the user security is applied so that no parameters except Pr
11.44
can be adjusted with
the LED keypad. When this parameter is read via an LED keypad and security is locked it appears as zero. The security code can be modified via
serial comms etc. by setting this parameter to the required value, setting Pr
11.44
to 3 and initiating a reset by setting Pr
10.38
to 100. However
security can only be cleared via the LED keypad.
This parameter indicates the continuous industrial current rating of the drive for heavy-duty operation. If this parameter is programmed into the level
two area, the decimal place on the drives four digit display will be adjusted to 1 for drive sizes with current ratings greater than 99.99A.
This parameter has four possible values and indicates the output voltage rating of the drive.
0
: 200
200V product
1
: 400
400V product
2
: 575
575V product
3
: 690
690V product
See Pr
This parameter indicates the version of DSP software installed.
11.30
User security code {25}
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
1
1
1
1
1
Range
0 to 999
Default
0
Update rate
Background
11.31
Unused parameter
11.32
Maximum heavy duty drive current rating
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
2
1
1
1
1
Range
0.00 to 290.00 A
Update rate
N/A
11.33
Drive voltage rating
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
1
1
1
1
1
Range
200(0), 400(1), 575(2), 690(3)
Update rate
N/A
11.34
Software sub-version
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
1
1
1
1
Range
0 to 99
Update rate
N/A
11.35
DSP software version
Coding
Bit
SP
FI
DE Txt VM DP ND RA NC NV
PT
US RW BU PS
1
1
1
1
1
Range
0.0 to 9.9
Update rate
N/A
11.36 to 11.40
Unused parameters