Menu 10
128
Commander SK Advanced User Guide
www.controltechniques.com Issue Number: 9
10.11 Menu 10: Status logic and diagnostic information
Table 10-16 Menu 10 parameters: single line descriptions
Parameter
Range
Default
Setting
Update Rate
10.01
Drive ok
OFF(0) or On(1)
B
10.02
Drive active
OFF(0) or On(1)
B
10.03
Zero speed
OFF(0) or On(1)
B
10.04
Running at or below minimum speed
OFF(0) or On(1)
B
10.05
Below set speed
OFF(0) or On(1)
B
10.06
At speed
OFF(0) or On(1)
B
10.07
Above set speed
OFF(0) or On(1)
B
10.08
Load reached
OFF(0) or On(1)
B
10.09
Drive output is at current limit
OFF(0) or On(1)
B
10.10
Regenerating
OFF(0) or On(1)
B
10.11
Dynamic brake active
OFF(0) or On(1)
B
10.12
Braking resistor alarm
OFF(0) or On(1)
B
10.13
Direction commanded
OFF(0) or On(1)
B
10.14
Direction running
OFF(0) or On(1)
B
10.15
Mains loss detected
OFF(0) or On(1)
B
10.16
Not used
10.17
Overload alarm
OFF(0) or On(1)
B
10.18
Drive temperature alarm
OFF(0) or On(1)
B
10.19
General drive alarm
OFF(0) or On(1)
B
10.20
Last trip
{55}
0 to 232
On drive trip
10.21
Trip 1
{56}
0 to 232
On drive trip
10.22
Trip 2
{57}
0 to 232
On drive trip
10.23
Trip 3
{58}
0 to 232
On drive trip
10.24
Trip 4
0 to 232
On drive trip
10.25
Trip 5
0 to 232
On drive trip
10.26
Trip 6
0 to 232
On drive trip
10.27
Trip 7
0 to 232
On drive trip
10.28
Trip 8
0 to 232
On drive trip
10.29
Trip 9
0 to 232
On drive trip
10.30
Full power braking time
0.00 to 320.00 s
0.00
B
10.31
Full power braking period
0.0 to 1500.0 s
0.0
B
10.32
External trip
OFF(0) or On(1)
OFF(0)
B
10.33
Drive reset
OFF(0) or On(1)
OFF(0)
21 ms
10.34
No. of auto reset attempts
0 to 5
0
B
10.35
Auto reset delay
0.0 to 25.0 s
1.0
B
10.36
Hold ‘drive ok’ until last attempt
OFF(0) or On(1)
OFF(0)
B
10.37
Action on trip detection
0 to 3
0
B
10.38
User trip
0 to 255
0
B
10.39
Braking energy overload accumulator
0.0 to 100.0%
B
10.40
Status word
0 to 32767
B