OPERATION 

CHECK THERMOSTAT OPERATION

If  at  any  time  during  testing  your  system  does  not  operate 
properly, contact a qualified service person.
Turn on power to the system.

Fan Operation

If your system 

does not

 have a 

G

 terminal connection, skip to 

Heating System

.

1.  Move fan switch to 

ON

 position. The blower should begin to 

operate.

2.  Move fan switch to 

AUTO

 position. The blower should stop 

immediately.

Heating System

1.  Move  SYSTEM  switch  to 

HEAT

  position.  If  the  auxiliary 

heating system has a standing pilot, be sure to light it.

2.  Press 

 to adjust thermostat setting to 1° above room 

temperature. The heating system should begin to operate.  

3.  Press 

  to  adjust  temperature  setting  below  room 

temperature. The heating system should stop operating.

To prevent compressor and/or property damage, if the 
outdoor  temperature  is  below  50

o

F,  DO  NOT  operate 

the cooling system.

CAUTION

!

Do  not  allow  the  compressor  to  run  unless  the 
compressor  oil  heaters  have  been  operational  for  6 
hours and the system has not been operational for at 
least 5 minutes.

CAUTION

!

Cooling System

1.  Move SYSTEM switch to 

COOL 

position.

2.  Press 

  to  adjust  thermostat  setting  below  room 

temperature. The blower should come on immediately on 
high speed, followed by cold air circulation. However, if the 
setpoint  temperature  is  flashing,  the  compressor  lockout 
feature is operating (see Configuration menu, item 5).

3.  Press 

  to  adjust  temperature  setting  above  room 

temperature. The cooling system should stop operating.

Summary of Contents for 1F86-0244

Page 1: ...el Programming Choice 1F86 0244 Non Programmable SPECIFICATIONS Electrical Rating Battery Power mV to 30 VAC 50 60 Hz or DC Input Hardwire 20 to 30 VAC Terminal Load 1 0 A per terminal 1 5A maximum all terminals combined Setpoint Range 45 to 90 F 7 to 32 C Differential Single Stage Heat 0 6 F Cool 1 2 F adjustable Differential Heat Pump Heat 1 2 F Cool 1 2 F adjustable Operating Ambient 32 to 105 ...

Page 2: ...on O B TERMINAL SWITCH SELECTION The O B switch on this thermostat is factory set to the O position This will accommodate the majority of heat pump applications which require the changeover relay to be energized in COOL If the thermostat you are replacing or the heat pump being installed with this thermostat requires a B terminal to energize the changeover relay in HEAT the O B switch must be move...

Page 3: ...rcuits are in only one of the systems remove the transformer of the system with NO safety circuits NOTE Optional Jumper for Single Stage Heat Pump R C G W Figure 4 Typical wiring diagram for two transformer single stage systems with safety circuits in BOTH systems Changeover Relay Y O B Compressor Contactor Changeover Relay is energized in COOL when O B switch is in the O position Changeover Relay...

Page 4: ...isplays current temperature Figure 5 Thermostat display buttons and switches SYSTEM 2 1 3 4 5 6 7 8 9 11 10 9 Service indicatesadiagnosticfaultintheheating cooling system It does not indicate a fault in the thermostat 10 Change Filter is displayed when the system has run for the programmed filter time period as a reminder to change or clean your air filter 11 indicates power level of batteries Cha...

Page 5: ...gle Stage Heat is Medium Cycle ME For Single Stage Cool the default setting is fast FA To change cycle rate press the and buttons The cycle rate differentials for different settings are MODE Fast Medium Slow FA ME SL SS Heat 0 6 F 0 8 F 1 2 F SS Cool 1 2 F 1 7 F 5 Select Compressor Lockout CL OFF or ON Selecting CL On will cause the thermostat to wait 5 minutes between cooling cycles This is inten...

Page 6: ...ate 3 Press to adjust temperature setting below room temperature The heating system should stop operating To prevent compressor and or property damage if the outdoor temperature is below 50o F DO NOT operate the cooling system CAUTION Do not allow the compressor to run unless the compressor oil heaters have been operational for 6 hours and the system has not been operational for at least 5 minutes...

Page 7: ... to thermostat or system 3 Cooling System requires service or thermostat requires replacement Set System Switch to Cool and lower setpoint below room temperature Verify thermostat and system wires are securely at tached Same procedures as diagnostic for No Heat condition except set the thermostat to Cool and lower the setpoint below the room temperature There may be up to a five minute delay befor...

Page 8: ...www white rodgers com White Rodgers is a division of Emerson Electric Co The Emerson logo is a trademark and service mark of Emerson Electric Co Homeowner Help Line 1 800 284 2925 ...

Page 9: ...ite rodgers com White Rodgers es una división de Emerson Electric Co El logotipo de Emerson es una marca comercial y una marca de servicio de Emerson Electric Co Línea de ayuda para el usuario 1 800 284 2925 ...

Page 10: ...calefacción esté funcionando correctamente El sistema no enfría 1 El interruptor System no está ajustado en Cool 2 La conexión al termostato o al sistema está suelta 3 El sistema de enfriamiento requiere servicio técnico o debe cambiarse el termostato Ajuste el interruptor System en Cool y baje la temperatura de referencia por debajo de la temperatura ambiente Verifique que los cables del termosta...

Page 11: ...e la temperatura por debajo de la temperatura ambiente El sistema de calefacción debería dejar de funcionar Para evitar daños al compresor y o daños materiales si la temperatura externa está por debajo de los 50 F NO utilice el sistema de enfriamiento PRECAUCIÓN No deje que el compresor funcione a menos que los calentadores de aceite del compresor hayan estado en funcionamiento durante 6 horas y q...

Page 12: ... FA Para cambiar la velocidad del ciclo presione el botón y el botón Las velocidades de los ciclos son las indicadas a continua c ión según la opción elegida MODO Rápido Medio Lento FA ME SL SS Heat 0 6 F 0 8 F 1 2 F SS Cool 1 2 F 1 7 F 5 Selección de bloqueo del compresor CL en OFF u ON Si se selecciona CL On el termostato esperará 5 minutos entre ciclos de enfriamiento para evitar que el compres...

Page 13: ...talla botones e interruptores del termostato SYSTEM 2 1 3 4 5 6 7 8 9 11 10 8 Muestra la temperatura actual 9 Service servicio indica una falla en el sistema de calefacción enfriamiento No indica una falla del termostato 10 Change Filter cambiar filtro aparece cuando el sistema se ha utilizado por la cantidad de tiempo seleccionada en el filtro para recordarle que debe cambiar o limpiar el filtro ...

Page 14: ... en uno de los sistemas retire el transformador del sistema SIN circuitos de seguridad NOTA Puente opcional para bomba de calor de una sola etapa R C G W Y O B 24 VCA 120 VCA VIVO NEUTRO VIVO NEUTRO NEUTRO NEUTRO Figura 4 Diagrama de conexiones típico para sistemas de una sola etapa de dos transformadores con circuitos de seguridad en AMBOS sistemas Relé de conmutación Contactor del compresor Relé...

Page 15: ...tato viene ajustado de fábrica en la posición O Esta opción admite la mayoría de las aplicaciones de bomba de calor que requieren que el relé de conmutación esté energizado en COOL Si el termostato que está cambiando o la bomba de calor que está instalando con este termostato requiere una terminal B para energizar el relé de conmutación en HEAT el interruptor O B debe colocarse en la posición B Or...

Page 16: ...e programación 1F86 0244 No Programable ESPECIFICACIONES Características eléctricas Alimentación con pilas mV a 30 VCA 50 60 Hz o CC Entrada Cableado interno 20 a 30 VCA Carga en terminales 1 0 A por terminal 1 5 A máx en todas las terminales combinadas Rango de temperatura de referencia 45 a 90 F 7 a 32 C Diferencial una sola etapa Calor 0 6 F frío 1 2 F ajustable Diferencial bomba de calor Calor...

Reviews: