Symptom 

Possible Cause

Corrective Action 

No Heat/ 

No Cool/

No Fan 

(common problem)

1.)

 Blown fuse or tripped circuit 

breaker

2.) 

Furnace power switch to OFF

3.)

 Furnace blower compartment 

door panel loose or not properly 

installed

4.)

 Loose connection to thermostat 

or system 

1.)

 Replace fuse or reset breaker 

2.)

 Turn switch to ON 

3.)

 Replace door panel in proper position to 

engage safety interlock or door switch 

4.)

  Tighten Connections 

No Heat 

1.)

 System Switch not set to Heat

2.) 

Loose connection to thermostat 

or system

3.)

 Heating System requires 

service or thermostat requires 

replacement

Verify thermostat and system wires are securely 

attached.

Diagnostic: Set System Switch to Heat and raise 

the setpoint above room temperature. Within five 

minutes the thermostat should make a soft click 

sound and “Heat On” should appear on display. 

This sound indicates the thermostat is operating 

properly. If the thermostat does not click, try 

the reset operation listed after this charting. 

If the thermostat does not click after being 

reset, contact your heating and cooling service 

person or place of purchase for a replacement. 

If the thermostat clicks, contact the furnace 

manufacturer or a service person to verify the 

heating system is operating correctly.

No Cool

1.)

 System Switch not set to Cool

2.) 

Loose connection to thermostat 

or system

3.)

 Cooling System requires 

service or thermostat requires 

replacement

Verify thermostat and system wires are securely 

attached.

Diagnostic: Set System Switch to Cool and 

lower setpoint below room temperature. Same 

procedures as diagnostic for “No Heat” condition 

except set the thermostat to Cool and lower the 

setpoint below the room temperature. There may 

be up to a five minute delay before the thermostat 

clicks in Cooling if the compressor lock-out option 

is selected in the installer menu. (see INSTALLER 

MENU, item 50)

Heat, Cool or Fan 

Runs Constantly

Possible short in wiring, thermostat, 

heat, cool or fan system

Check each wire connection to verify they are not 

shorted or touching other wires. Try resetting the 

thermostat. If the condition persists contact your 

HVAC service person.

Thermostat 

Display & 

Thermometer 

Disagree

Thermostat display requires 

adjustment

Display can be ad/-

5

°. See User Menu 

item 

04

(Troubleshooting continued on next page)

 TROUBLESHOOTING

Resetting the Thermostat or Thermostat Settings

If the thermostat has good batteries, but has a blank display or does not respond to key 

presses, the thermostat should be reset by removing the batteries for

 2 

minutes. This reset 

will not change the menu settings or program. If the condition persists after reinstalling the 

batteries, replace the thermostat. 
To conveniently reset only the schedule and user settings back to factory defaults, press Menu 

and Backlight buttons at the same time and hold until the display goes blank and resets. 

HOMEOWNER HELP LINE:

 1-800-284-2925

White-Rodgers is a business  
of Emerson Electric Co.

The Emerson logo is a 
trademark and service mark  
of Emerson Electric Co. 

www.white-rodgers.com

www.emersonclimate.com

TROUBLESHOOTING (C0ntinued)

Symptom 

Possible Cause

Corrective Action 

Furnace (Air 

Conditioner) 

Cycles Too Fast or 

Slow (narrow or 

wide temperature 

swing) 

The location of the thermostat and/

or the size of the Heating System 

may be influencing the cycle rate

Digital thermostats provide precise control and 

cycle faster than older mechanical models. The 

system turns on and off more frequently, but runs 

for a shorter time. If you would like to increase 

cycle time, choose SLO for slow cycle in the 

Installer menu. (Reference menu items 

30 & 35

) If 

an acceptable cycle rate is not achieved, contact 

your HVAC service person.

“Call for Service” 

icon appears on 

displayed

1.)

 Heating system is not able to heat 

the space to within 

10 

degrees of 

the setpoint within 

2

 hours

2.)

 Cooling system is not able to cool 

the space to within 

10

 degrees of 

the setpoint within

 2

 hours

3.)

 If “--” is displayed for the Room 

Temperature, a replacement 

thermostat is needed

4.)

 None of the buttons operate on 

the thermostat

5.)

 If “Call for Service” is flashing, 

compressor self diagnostic is 

detecting an issue with the 

outdoor unit

1.) 

See corrective action for “No Heat”

2.)

 See corrective action for “No Cool”

3.) 

Replace thermostat

4.)

 Make sure keypad lockout is not turned on 

(denoted by   icon) 

5.)

 Contact a service person to verify the 

equipment is operating correctly

Summary of Contents for 1F83H-21NP

Page 1: ...H 2 Terminal Designations Terminal Function R Power 24V O B ChangeoverTerminal Energized in Cool O or Heat B for Heat Pump or Damper Systems Y Heat and Cool Mode 1st Stage Compressor G Fan Relay E Auxiliary only Heat Mode Emergency Heat C Common wire for 24V optional with batteries L Heat Pump malfunction Diagnostic terminal input signal requires common W2 Heat Mode 2nd stage CutW2 E jumper when s...

Page 2: ... operational for 6 hours and the system has not been operational for at least 5 minutes TEST EQUIPMENT Turn on power to the system Fan Operation If your system does not have a G terminal connection skip to Heating System 1 Move fan switch to On position The blower should begin to operate 2 Move fan switch to Auto position The blower should stop immediately Heating System 1 Move System Switch to He...

Page 3: ...ERMOSTAT Whenever Replace appears in the display new premium brand AA alkaline batteries should be installed If the house will be unoccupied for an extended period and either or Replace is displayed install new batteries before leaving 6 USER MENU To customize thermostat settings press the Menu button from the home screen Use Next to advance through menu items Press or to change the setting User s...

Page 4: ... contact your HVAC service person Thermostat Display Thermometer Disagree Thermostat display requires adjustment Display can be adjusted 5 See User Menu item 04 Troubleshooting continued on next page TROUBLESHOOTING Resetting theThermostat orThermostat Settings If the thermostat has good batteries but has a blank display or does not respond to key presses the thermostat should be reset by removing...

Reviews: