Emerson 1301G Instruction Manual Download Page 4

Types 1301F and 1301G

4

Installation

!

WARNING

Overpressuring a regulator or 

associated equipment may cause 

leakage, part damage or personal injury 

due to bursting of pressure containing 

parts or explosion of accumulated gas. 

Do not install a regulator where service 

conditions can exceed the specifications 

listed on the Specifications section, or 

any applicable local, state or federal 

codes and regulations.

Use qualified personnel when installing, operating and 

maintaining these regulators. Make sure that there 

is no damage or foreign material in the regulator and 

that all tubing and piping are clean and unobstructed. 

The regulator may be installed in any position. Apply 

pipe compound to the pipeline threads. Connect inlet 

piping or tubing to the 1/4 NPT connection marked 

“In” and outlet piping or tubing to one of the 1/4 NPT 

connections marked “Out”. Install a pressure gauge or 

pipe plug in the unused outlet connections.
If continuous operation of the system is required 

during inspection or maintenance, install a three-valve 

bypass around the regulator.

!

WARNING

A regulator may vent some gas to 

the atmosphere. In hazardous gas 

service, vented gas may accumulate, 

causing personal injury or equipment 

damage due to fire or explosion. Vent 

a regulator in hazardous gas service to 

a remote, safe location.

The optional stainless steel spring case of the 

Type 1301F regulator has one 1/4 NPT internal 

connection. The Type 1301G regulator spring case 

has one 1/8 NPT internal connection with a screen. To 

remotely vent the spring case, remove the screen, if 

present, and connect 1/4 or 1/8 NPT piping or tubing 

to the spring case connection. The piping or tubing 

should vent the spring case to a safe location, have as 

few bends as possible, and have a screened vent on its 

exhaust end.
Each regulator is factory-set for the pressure setting 

specified on the order. If no setting is specified, outlet 

pressure is factory-set at the midpoint of the regulator 

spring range. If pressure adjustment is necessary, refer 

to the Startup section. In all cases, check the spring 

setting to make sure it is correct for the application.

Overpressure Protection

The 1301 Series regulators have an outlet pressure 

rating lower than their inlet pressure rating. If actual 

inlet pressure can exceed the outlet pressure rating, 

outlet overpressure protection is necessary. However, 

overpressuring any portion of the regulators beyond 

the limits in Specifications section may cause leakage, 

damage to regulator parts or personal injury due to 

bursting of pressure-containing parts.

Some type of external overpressure protection should be 

provided if inlet pressure will be high enough to damage 

downstream equipment. Common methods of external 

overpressure protection include relief valves, monitoring 

regulators, shutoff devices and series regulation.

If the regulator is exposed to an overpressure 

condition, it should be inspected for any damage that 

may have occurred. Regulator operation below these 

limits does not preclude the possibility of damage from 

external sources or from debris in the pipeline.

Startup

With installation completed and downstream 

equipment adjusted, slowly open the upstream and 

downstream block valves while using pressure gauges 

to monitor pressure.

If adjustment is necessary, loosen the locknut 

 

(key 18, Figures 3 and 4), and turn the adjusting 

screw (key 15, Figures 3 and 4) clockwise to 

increase the set pressure or counterclockwise to 

decrease the set pressure. Monitor pressure with 

gauges during adjustment. When adjustment is 

complete, tighten the locknut. If the desired outlet 

pressure is not within the range of the regulator 

spring, install a spring with a desired range 

according to the Maintenance section.

Shutdown

First, close the upstream shutoff valve, and then, 

close the downstream shutoff valve. Next, open 

the vent valve between the regulator and the 

downstream shutoff valve and open the vent valve 

between the regulator and the upstream shutoff 

valve. If vent valves are not installed, safely bleed 

off both inlet and outlet pressures and check that 

the regulator contains no pressure.

Summary of Contents for 1301G

Page 1: ...alified personnel when installing operating and maintaining the 1301 Series high pressure regulator Introduction Scope of the Manual This Instruction Manual provides instructions for the installation adjustment maintenance and parts ordering of the Types 1301F and 1301G high pressure regulators Product Description Types 1301F and 1301G regulators are direct operated high pressure regulators which ...

Page 2: ...ef Valve Sizing Cg 5 0 Cv 0 13 C1 38 5 Specifications Specifications section lists the specifications for Types 1301F and 1301G high pressure regulators The maximum outlet pressure for a given regulator as it comes from the factory is stamped on the regulator nameplate IEC Sizing Coefficients XT 0 938 FD 0 50 FL 0 85 Recovery Coefficient Km 0 72 Material Temperature Capabilities 1 Nylon PA Valve D...

Page 3: ...ring force which is sensed by the diaphragm moving the yoke and disk assembly up near its orifice restricting flow across the regulator M1015 INLET PRESSURE OUTLET PRESSURE ATMOSPHERIC PRESSURE Type 1301F Figure 2 Type 1301F Operational Schematic TYPE OUTLET PRESSURE RANGES 1 SPRING COLOR SPRING PART NUMBER SPRING WIRE DIAMETER SPRING FREE LENGTH psig bar In mm In mm 1301F 10 to 75 0 69 to 5 2 Blu...

Page 4: ...ator spring range If pressure adjustment is necessary refer to the Startup section In all cases check the spring setting to make sure it is correct for the application Overpressure Protection The 1301 Series regulators have an outlet pressure rating lower than their inlet pressure rating If actual inlet pressure can exceed the outlet pressure rating outlet overpressure protection is necessary Howe...

Page 5: ...alves are a matched set and need to be kept together 10 Unscrew the orifice key 5 Examine seating edge of orifice Replace with a new part if worn or nicked Assembly This procedure assumes that the regulator was completely disassembled If not start these instructions at the appropriate step Key numbers used are shown in Figure 3 for the Type 1301F regulator and in Figure 4 for the Type 1301G regula...

Page 6: ...e Regulator Assembly 15 2 11 19 16 1 13 14 3 22 10 6 5 4 12 17 7 8 9 18 CN7095_C 6 15 2 11 19 16 1 13 14 3 22 10 5 4 12 17 7 8 9 18 21 19 8 7 17 4 13 BP6341 A Figure 5 Exploded View of The Diaphragm Head Assembly and Yoke 20 40 S 6 0 0 0 P S I M A X I N L E T F I S H E R M AX OUTLET PSI U S A NOTE OPTIONAL THIRD OUTLET ...

Page 7: ...d Type 1301G 1 8 NPT vent connection Standard or with T Handle Brass 2P195713022 316 Stainless steel 21A6377X012 3 Bottom Cap Brass 1D468513012 304 Stainless steel 1J919635072 316 Stainless steel NACE 1J9196X0032 4 Yoke Brass 1D383313012 316 Stainless steel NACE 1J925936042 5 Orifice 303 Stainless steel 1D386535032 316 Stainless steel NACE 1D3865X0032 6 Valve Disk Assembly Brass Nylon PA 1D4684000...

Page 8: ... Headquarters Elk River Minnesota 55330 2445 USA Tels 1 763 241 3238 1 800 447 1250 Europe Selmsdorf 23923 Germany Tel 49 38823 31 287 Asia Pacific Shanghai 201206 China Tel 86 21 2892 9499 For further information visit www fisherregulators com Key Description Part Number 17 Machine Screw 2 required Steel for brass yoke 1H526928982 302 Stainless steel for Stainless steel yoke 1J926938992 18 Locknu...

Reviews: