d. Route AC supply leads throught the top or side hole of housing. 

Note: to avoid shadowing secure wires into wire guides located on 
the sides of the housing.     

4. Make the proper connections (see figure 6): 

a.   For 120VAC, connect the black wire (120VAC) and white (neutral) 

to the building utility. 

b. For 277VAC, connect the orange wire (277VAC) and white (neutral) 

to the building utility. 

CAUTION! 

Risk of electrical shock.

 

Cap unused wires. In all cases, 

use suitable wire nuts rated for the applicable voltage to connect to 
wires.  

c. Feed wires back into the junction box and secure the canopy to the 

crossbar so that the canopy is tight against the wall or ceiling.          

5. Snap chevrons to the EXIT panel if required.

6. For self-powered units attach battery connectors togeather.

7. Reinstall the front panel.

Self-Powered Models

For test procedures refer to addendum for self-dianostics and self-testing 
option.

Maintenance

None required. If AC supply to the unit is to be disconnected for 2 months 
or more, the battery must be disconnected, Self-Powered Models only. 
Equipment must be tested regularly in accordance with local codes.

Figure 7

1) Manual battery test switch
2) Red LED (indicates normal operation

Gre

en grou

nd wire

Whit

e neut

ral

Black 120V

A

C

O

range

 2

77V

AC

Figure 6

Figure 5

Insert canopy into housing at 20 degree angle and 
twist. Quick snap is now locked firmly.

Caution:

 Trying to remove the canopy after it is 

locked into place may cause damage.

Figure 8

Note: battery is shipped disconnected
Connect battery before closing unit