EMC-PAC User Guide 

 

 

 

- 6 - 

Description of Operation 

The EmerCom Power and Alarm Consolidator (EMC-PAC) board allows for the easy 
termination of the Phone Line Monitoring (PLM) alarm outputs built into the EmerCom 
EMC-60 Hands-free Elevator phones.  The EMC-PAC board can accept PLM wiring 
from up to 4 phones and allows the alarms to be combined as one or two groups. 

When attached to a 12V SLA battery, the EMC-PAC board provides backup power to 2 
EMC-ALRM boards during a power outage. 

A green POWER ON LED in the middle of the board quickly informs personal that the 
board has power and is operational.  Whenever the red REPLACE BATTERY, NO 
MAINS, or FAULT status LEDs illuminate, there exists one or more issues with the 
wiring or battery.  The issue can be quickly identified by reading the name of the status 
LED or by looking up the problem in the troubleshooting section. 

Additional red LEDs exist at each STN and each GROUP terminal to aid the technician 
with the different conditions.  When an LED illuminates red, the corresponding terminal 
is in an alarm condition.  Alarms on the EMC-PAC are based on fail-safe conditions and 
detect an alarm when the terminals are “open-circuit”. 

The EMC-PAC comes equipped with an audible buzzer that emits a short tone 
whenever the board needs servicing such as battery replacement. 

Configuring Groups 

STN #1 PLM alarm can only be configured as GROUP A or GROUP B. 

STN #2 through STN #4 can be configured as GROUP A, GROUP B, or DISABLE. 

Ensure that the provided shunt is properly attached to the pins as shown below. 

GROUP

A   B

DISABLE

GROUP

A   B

DISABLE

GROUP

A   B

DISABLE

GROUP

A   B

DISABLE

GROUP

A   B

DISABLE

GROUP

A   B

DISABLE

GROUP

A   B

DISABLE

GROUP

A   B

DISABLE

GROUP

A   B

DISABLE

GROUP A

GROUP B

DISABLE

 

 

Summary of Contents for EMC-60

Page 1: ...EMC PAC USER GUIDE Power and Alarm Consolidator...

Page 2: ...to BAT 2 3 4 Connect first station phone line alarm STN 1 to PLM on EMC 60 phone Connect additional stations as required STN X to PLM on EMC 60 phon 1 Troubleshoot alarms if any POWER ON for normal o...

Page 3: ...Specifications 8 Ordering 8 Warranty 9 About the EMC PAC Power Alarm Consolidator Board Key Features Uninterruptable power supply UPS for up to two EMC ALRM boards Consolidates the phone line alarm o...

Page 4: ...4 STN 3 STN 2 STN 1 PWR IN BAT PWR OUT GRP A GRP B PWR CALL CALL LED LED TEL TEL PLM PLM LED2 AUX MIC SPKR ALARM BATT SD Card 1 4 7 2 5 8 0 3 6 9 LINE TEST CANCEL REPLAY ENTER PROGM SPKR SPKR ALARM S...

Page 5: ...uide 5 EMC ALRM and EMC PAC Low Rise Layout Group B Group A Telco Phone Line EMC PAC 110 V AC EMC 60 Hands free phones in elevator cabs EMC ALRM EMC ALRM Shielded Twisted Pair STP battery 110V Supply...

Page 6: ...ed by reading the name of the status LED or by looking up the problem in the troubleshooting section Additional red LEDs exist at each STN and each GROUP terminal to aid the technician with the differ...

Page 7: ...load on PWR OUT Contact Support 1 844 363 7266 Dimensions 16 5 24VAC 16 28VDC 12V SLA 1200mAh fuse 1A fast MAINS BYPASS BUZ EmerCom Technologies Inc 1 844 363 7266 CONNECT TO EMC ALRM CON NECT TO EMC...

Page 8: ...end of the traveling cable Output Power 12Vdc typical 200mA max Input Power 16 5 24Vac 16 28Vdc Battery Type Sealed Lead Acid Rated Voltage 12V Capacity 1 2AH Terminals 0 187 spade Operating Range 0...

Page 9: ...7266 for a Return Authorization RMA number Please provide Model number Problem or fault description Name of the person requesting the RMA phone number and shipping address Please reference the RMA nu...

Page 10: ...EMC PAC User Guide 10 Rev 1p0a...

Reviews: