Installing a cluster
23
Installing the Hardware
5. From the front of the cabinet, remove each engine’s bezel as shown in
,
and verify that the two power supply modules, four fan modules, and solid state
drive (SSD) enclosure are fully inserted and secure.
Figure 7
Engine components: Front view
Task 3: Stabilize the
equipment
The equipment requires time to become acclimated to a data center environment.
lists the required times.
a. Temperature and humidity values must be such that condensation does not occur on any VPLEX component.
CL4341c
!
!
Power s
u
pply
Fan
SSD enclos
u
re
Table 2
Data center acclimation times
Transit/storage environment
Hours required
before applying
power
Condition
Temperature range
Relative humidity
Nominal
68
o
to 72
o
F (20
o
to 22
o
C)
Less than 30%
0
Cool / Damp
Less than 68
o
F (20
o
C)
30% or greater
4
Cold / Dry
Less than 20%
Hot / Dry
72
o
to 90
o
F (22
o
to 32
o
C)
Less than 30%
Hot / Humid
30% to 45%
45% to 60%
8
60% to 80%
16
Summary of Contents for VPLEX
Page 8: ...EMC VPLEX with GeoSynchrony 4 1 Installation and Setup Guide 8 Tables...
Page 20: ...EMC VPLEX with GeoSynchrony 4 1 Installation and Setup Guide 20 Introduction...
Page 76: ...EMC VPLEX with GeoSynchrony 4 1 Installation and Setup Guide 76 Setting up VPLEX...
Page 92: ...EMC VPLEX with GeoSynchrony 4 1 Installation and Setup Guide 92 Reference...
Page 94: ...EMC VPLEX with GeoSynchrony 4 1 Installation and Setup Guide 94 Index...