14
6.3. Particle and magnetic flow filter (3)
1. The particle and magnetic flow filter requires
cleaning at least once a year, when necessary or
when throughput is inadequate.
2. Close the ball valves on input (2) and output (12)
3. Unscrew black magnet (A) from the filter and
pull it out
4. Open dirty water drain valve (B)
5. Unscrew filter casing (C)
6. Remove the filter
7. Clean the filter and casing with water
8. Check the seal
9. Replace the filter in filter casing (C) and refit it
10. Screw in magnet (A)
11. Close dirty water drain valve (B)
6.4. Fine mesh filter
Fine mesh filter (10) requires cleaning once a year or when throughput is
inadequate.
1.
Disconnect reinforced hose (7) on the right-hand side of the device (not
on the head)
2.
Undo the brass coupling
3.
Clean the fine mesh filter with water
4. Refit the fine mesh filter and brass coupling
5. Reconnect reinforced hose (7)
B
A
C