elysator PUROTAP profi 1 Series Installation Function Operation Service Download Page 12

12

measures no throughput for about one hour, it automatically switches off. 

During operation with the optional power supply unit, the combined meter 

does not automatically switch off and cannot be switched off manually. If the 

combined meter has switched off automatically, it will automatically restart 

once the throughput (> 2 l / min) resumes. If the combined meter is switched 

off using the ON/OFF key, it will not restart automatically. 

Auto mode

Press the   key

 

twice in quick succession to start automatic monitoring by 

the combined meter. The 

 symbol is shown to indicate that monitoring 

has been enabled. In auto mode, the meter only takes measurements when 

water is actually passing over it. If the throughput is interrupted, the meter 

continues to show the last captured value. When a throughput is present, the 

meter takes a new reading of the conductivity value after every 10 litres and 

displays it. If the limit is exceeded in two successive measurements, the 

display continuously flashes red and an acoustic alarm sounds. In addition, 

the floating contact is switched over. If the   key is pressed for a third time, 

the meter exits auto mode.

Litre-gallon key

Briefly press this key once to select the throughput indication in litres per 

minute (l / min) or gallons per minute (GPM).

 

Press the key for approx. 3 seconds to reset the total throughput volume 

("JOB") to 0. We recommend resetting the "JOB" to 0 after every resin change 

so that the residual capacity of the ion exchange resin can be estimated and 

compared. The TOTAL litres cannot be reset to 0!

5.5. Fill water quality indicator (11)

The fill water quality is indicated using the traffic light principle.

 

Green   =  

Resin is ready for operation

 

Amber  =  

Resin will soon be spent

 

Red    =  

Resin must be replaced

Summary of Contents for PUROTAP profi 1 Series

Page 1: ...www elysator com Operating instructions PUROTAP profi 1 Installation Function Operation...

Page 2: ......

Page 3: ...1 2 Filling the resin canister 8 5 2 1 Connection for system filling 9 5 2 2 Connection for system flushing 9 5 3 1 Commissioning 10 5 3 2 Pressure reducing valve 10 5 4 Combined meter 10 5 5 Fill wat...

Page 4: ...4 1 Safety instructions Must be supervised Please note Not drinking water 25 l min Flow rate max 25 l min Maximum 4 bar pressure up to 60 C Maximum 6 bar pressure up to 25 C 6 bar...

Page 5: ...demineralises water using a mixing bed ion exchange resin The device has integral meters that constantly measure and display fill volume throughput and water quality There is no need for an external...

Page 6: ...and water quality 7 Reinforced hose 2x 8 Head with immersion pipe not shown 9 Resin canister 10 Fine mesh filter 11 Fill water quality indicator 12 Fill water output 3 4 with shut off valve 13 Drain v...

Page 7: ...o 60 C 4 bar up to 60 C 5 Operation 5 1 1 Replacing filling the resin 1 Close the ball valves on input 2 and output 12 2 Remove the mesh filter at drain valve 13 3 Connect a hose to drain valve 13 and...

Page 8: ...7 at the lower end i e on the device not the head 2 Grip head 8 with both hands and unscrew it from resin canister 9 3 Remove the head with immersion pipe 8 from the resin canister 4 Use the funnel t...

Page 9: ...low in the wrong direction Where DIN EN 1717 is applicable Germany additionally install a pipe separator upstream of the filling station Observe the water utilities regulations PUROTAP profi may only...

Page 10: ...auge to check the set pressure The filling pressure is displayed on pressure gauge 4 Adjust the pressure reducing valve to ensure that the system is not damaged during filling The maximum operating pr...

Page 11: ...y is measured for 10 seconds and compared to the set limit During measuring the screen backlighting is blue and the conductivity value is displayed If the measured value is below the set limit everyth...

Page 12: ...lue When a throughput is present the meter takes a new reading of the conductivity value after every 10 litres and displays it If the limit is exceeded in two successive measurements the display conti...

Page 13: ...d meter see the PUROTAP LFM 20 product page on our website 6 2 Changing the batteries on the fill water quality indicator The battery life is about 2 3 years After this period the batteries have to be...

Page 14: ...ng C 6 Remove the filter 7 Clean the filter and casing with water 8 Check the seal 9 Replace the filter in filter casing C and refit it 10 Screw in magnet A 11 Close dirty water drain valve B 6 4 Fine...

Page 15: ...0 872 PUROTAP profi 1 immersion pipe 100 968 100 739 PUROTAP profi 1 complete head 100 741 PUROTAP LFM 20 combined meter 102 278 PUROTAP profi 1 head O ring 100 255 PUROTAP i control for PUROTAP profi...

Reviews: