8.4. Checking and assessing the condition of the anodes
The sacrificial magnesium anode is located inside the strainer and can be
checked visually.
• Anode has a diameter < 10 mm or only a thin steel wire can be seen
Replace the anode.
• Anode still has a diameter > 10 mm but it is covered with a layer of dirt
Replace the anode.
• Anode still has a diameter > 10 mm
You can continue to use the anode.
8.5. Replacing the wear indicator and the control button
(Fig. 7.3.)
1.
Remove top cover panels (10)
2.
Remove contact blade (3) from the blade terminal
3.
Loosen flange screw (4) with cable connection
4. Remove self-tapping screws from duct (14)
5. Remove duct (14)
6. Replace wear indicator (2) or control button (13) as appropriate
7. Refit duct (14) and replace the screws
8. Tighten flange screw (4) with cable connection
9. Replace contact blade (3)
10. Refit top cover panels (10) using the screws
9. Spare parts
Designation
ELYSATOR®
Typ 50c
ELYSATOR®
Typ 75c
ELYSATOR®
Typ 100c
Anode fittings
101043
101044
101043
Flange gasket
101240
101240
101240
Air vent
100402
100402
100402
Wear indicator
100277
100277
100277