EQUIPMENT OPERATION
The dip switches control the following parameters:
The trimmers regulate the following parameters:
DIP
SLIDING
1
Automatic reclosure on/off
2
Opening mode:
off = condominium
on = open/stop/close
3
Pre-flashing On/Off
4
STPA input:
off = internal photocell
on = normal edge
5
Check photocells on/off
6
Pedestrian/2CAN:
off = pedestrian
on = 2CAN
7
Not used
8
Operating mode:
off = sliding
on = barrier
TRIMMER
SLIDING
1 (SENSE)
Obstacle sensitivity
2 (V.RALL)
Slow-down speed
3 (V.MAX)
Maximum speed
4 (AUX1)
Not used
Pressing the OPEN/CLOSE button activates the motor to open. If the automatic gate system is already open, pressing the button again closes it. If at least
one radio control has been programmed, when one of the buttons is pressed the green LED lights up briefly to indicate that the radio control has been re-
ceived correctly.
When the PEDESTRIAN OP button is pressed, the opening manoeuvre stops at a point equal to 30% of the total travel.
Pressing the same button again starts the closing manoeuvre. However if OPEN/CLOSE is pressed instead, the opening manoeuvre is completed.
When OPEN/CLOSE is pressed during pedestrian opening, the manoeuvre continues to the fully open position.
AUTOMATIC RECLOSURE
This function is controlled by dip switch 1. If it is active, the automatic gate system closes automatically after a time equal to:
• 30 seconds, if easy learning was used
• the time acquired during full learning
OPENING MODE
Opening mode is controlled by dip switch 2. The types of operation that can be set are:
• CONDOMINIUM: during opening the automatic gate system does not respond to other commands, e.g. it continues to open. However during closing,
a command causes it to reopen
• OPEN – STOP – CLOSE: during a manoeuvre, pressing the OPEN/CLOSE button stops the manoeuvre
FLASHING LIGHT
The flashing light illuminates intermittently during opening and closing manoeuvres. However it remains off when the gate is closed and whenever it stops
permanently. If the “automatic reclosure” and/or “immediate reclosure” parameters are configured, the flashing light remains on, indicating the imminent
activation of an automatic manoeuvre, e.g. reclosure. However if it flashes rapidly, this indicates a possible photocell fault.
AUX OUTPUT
The AUX output is activated when an opening request is received and remains active until the gate is shut.
ERROR SIGNALS
The following flashing light signals indicate whether an error has occurred. If the automatic gate system was moving, it stops and a certain number of fla-
shes are emitted according to the coding indicated in the following table:
Number of flashes
Meaning
2
Photocell test failed
3
Problem detected in the circuit that activates the motor
4
Problem in the encoder
5
Serious EEPROM error
6
Travel path end time elapsed
7
Fuse F2 blown