45
GB
VENTILATION/AIR SUPPLY
When the cabinet is running it produces 45 m³ of damp air per hour. You should therefore en-
sure that the room is well ventilated to replace the damp air that is extracted.
CONNECTING TO VENTILATION
The drying cabinet should be connected to a ventilation system that meets the relevant stan-
dards.
The drying cabinet can be connected to a ventilation duct in two ways, either by using
the ventilation adapter, or by connecting directly to a mechanical extractor .
If the drying cabinet is connected to an existing ventilation system the ventilation adapter must
always be used, to prevent interference with the general ventilation in the premises.
Direct connection should only be used when a dedicated extractor duct is provided for the dry-
ing cabinet.
The manufacturer recommends that the drying cabinet is connected using the ventilation
adapter .
1. With ventilation adapter
____________________________
Do not connect the drying cabinet to an exis-
ting chimney.
___________________________________
Make sure the air intake is not blocked
____________________________
1 Place the supplied collar
(4)
over the hole
in the top of the cabinet, insert the screws
and secure the collar.
2 Connect the flexible hose
(3)
to the collar.
Connect the other end of the hose to the
ventilation adapter
(5),
then secure this
over the exhaust vent in the room.
1. Damp air out
2. Air extracted from room
3. Flexible hose
4. Collar
5. Ventilation adaptor
6. Air intake
1
2
3
4
5
6
4