23
Quick Reference
The button functions appear as consecutive steps on pressing the corresponding button repeti-
tively. The first item indicates the display in its initial state The numbers in brackets indicate the
relevant section in the operating instructions. Calibration is described in Section 4.2
Normal operation (3) Buttons:
Indoor
Wind
Rain
Alarm
Sensor
Outdoor
Temperature Speed mph
Total
Active
Select
Temperature
Humidity
Speed, knots
Last hour
Alarm value
Outdoor sensor
Humidity
Dewpoint
Speed m/s
Last 24 hours
Display
Dewpoint
Humidity
Speed km/s
Alarm
Humidity
Wind direction
Windchill
Humidity
Button
Min/Max (3.4)
Arrow buttons (3.4) Reset
Program Mode (4)
Activate Program Mode by pressing the two arrow keys simultaneously
Display: PROGRAM MODE
Setting alarm min/max values (4.1)
Use the arrow buttons ‘<-’ or ‘->’, and the ‘Sensor’ button if necessary, to select the required
measuring point or measuring quantity.
Min/Max selection: Use the Min/Max buttons to enter any minimum or maximum values required.
The button functions and function sequence corresponds to the Min/Max function described abo-
ve. In this way, all the minimum values can be set at first then the maximum values, or the respec-
tive min. and max. values can be set on the individual sensor.
Set value: Use the ‘+’ and ‘-’ buttons to set the required values. Hold the button pressed in and the
unit automatically counts up or down, respectively.
Increase counter speed: The counting speed factor can be increased by 10 by pressing ‘+’ ‘-’
and ‘Sensor’ buttons simultaneously.
Calibration (4.2)
Calibration Mode, display: CALIBRATION (press the buttons ‘<-’ ‘Calibr’ and ‘->’ simultaneous-
ly). The display fields for air pressure sensor, rainfall transmitter and clock can be selected using
the ‘<-’ and ‘->’ buttons. The basic addresses of sensor assignments (4.5) can be changed and
display of temperature in
°
F or
°
C selected. The settings for height compensation regarding baro-
metric air pressure and correction of the calibration factor for the rainfall transmitter can be modi-
fied using the ‘+’ and ‘-’ buttons. The time and date are set according to Table 1.
Changing unit of measurement (4.3)
After pressing the ‘Unit’ button, the RAINFALL display can be set to in or mm, RELATIVE AIR
PRESSURE to inHg or hPa and temperature displays to
°
F or
°
C.
Display all minimum values
Display all maximum values
Pressed when min. or
max. values are display-
ed: individual display of
the stored values of the
individual measuring
points with date and time
of occurrence of the min.
and max. value
Press 2 s during normal operation
Delete accumulated rainfall total
Press 2 s when min. or max. values
are displayed: delete all stored values
(min. or max.)
Press 2 s during selective display via
the arrow buttons: Only delete min.
or max. value of the selected measu-
ring point.
Summary of Contents for WS 2010
Page 2: ...2...