Eltek TU 1004 User Instructions Download Page 6

Modbus configuration

The ModBus Setup menu allows the configuration of the ModBus node address and 

channel registers. Node Address should be set to the required 'Slave ID'. The following six 
boxes are for specifying addresses of holding registers for reporting the transmitter 

information. The value in each of these boxes must be greater than that in the previous 
box. Note the both the 'Reg' address boxes (Raw and Scaled) are only the start addresses 

for those registers, and gaps must be left after each of at least the number of channels 
configured in the RC250.

Field

Description

Node Address

ModBus slave ID

Raw Reg Address

Base address of Holding Registers for raw value from the sensor

Scaled Reg 

Address

Base address of Holding Registers for range-scaled value from the 

sensor

Scaling Address

Address of Holding Register for scaling factor

Battery Address

Address of Holding Register with the most recent battery level

Nbr Tx Address

Address of Holding Register containing transmitter serial number

Age Address

Base address of Holding Registers containing age of each value.

When reading the values from the RC250, the only Function Code that can be used is 'Read 

Holding Registers' (0x03). The registers containing the data start at the respective ‘Base 
Addresses' described above. When reading channel values, it is possible to read several at a 

time using the 'Quantity of Registers' field, but note that RC250 is limited to 50 registers at a 
time.

There was a convention that is still sometimes used with ModBus which refers to the 

Holding Registers in the form 4xxxx. With this scheme, what is referred to as 'Holding 
Register 40001' is actually addressed within the protocol as register address 0000 - not 
register address 0001. We always use the actual register address number that is encoded in 

the Modbus message (in this case 0000), and we do not use the '4xxxx' prefix. Occasionally 
you may come accross other manufacturer's systems that do not even correctly handle this 

offset of 1.

Example request to retrieve holding register 100 (set up to contain the raw value from 
channel 1) from node address 6:

Slave Address

06

Function

03

Starting Address Hi

00

Starting Address Lo

64

No. of Registers Hi

00

No. of Registers Lo

01

Page 6 of 8

Summary of Contents for TU 1004

Page 1: ...ot receive a message from a transmitter within a configured time the stored value will be set to no data For more detail see P6 No Data interval Example application Typically data from the RC250 to th...

Page 2: ...n the top of the RC250 Indicates the receiver has successfully received a valid data packet A single serial port on the PC can be used but this will mean having to change over the LCTX3 lead and LC68...

Page 3: ...es for ModBus communications See ModBus Configuration section Buttons Get TX Get the current configuration from the Transmitter Set Interval Set TX Interval use the drop down menu Set Sensor On Time A...

Page 4: ...equired Get the current or start a new RC250 Configuration using the button you should see the details appear in the right hand list box Now connect each transmitter to the PC using an LC TX3 programm...

Page 5: ...communications and should be investigated Nbr TX Is the number of successful transmissions received indicating reliability of performance and is for statistical purposes only Columns in the RX Config...

Page 6: ...ss Base address of Holding Registers containing age of each value When reading the values from the RC250 the only Function Code that can be used is Read Holding Registers 0x03 The registers containing...

Page 7: ...meaning 49 3 RH CRC Hi ac CRC Lo d9 Raw Reg Address Values other than pulse counts contain values less than 65000 Numbers starting from 65441 0xFFA1 are used to represent out of range or fault condit...

Page 8: ...dard optional accessory type LW ANT SMA The maximum recommended lead length is 10m Antenna compact Yagi Lightweight 3 element Yagi providing up to 6db gain optional supplied with 5m lead and plug Temp...

Reviews: