Quick Start Guide
Flatpack2 PS System, 4U, SP2-based
356825.103, 2v0 -2011-09
3
Installing Rectifiers and Opening
Smartpack2
Master
Installation
Removing Blind Panels
1.
Release the panel’s upper left and right corners
by
inserting a small screwdriver into the panel’s upper left gap and carefully press
down and out to release the locking tabs. Repeat on the upper right gap.
2.
Remove the blind panel
by
using you hand to pull the panel loose
Mounting Blind Panels
1.
Insert the panel’s upper
edge by
pressing gently so that its upper locking tabs engage
2.
Lock the panel’s lower
edge by
pressing with your hand so that the blind panel’s lower tabs lock into position.
Mounting or Removing
Flatpack2
Rectifiers
For an overview of available rectifiers, refer to “User Guide
Flatpack2
Rectifier
Modules”, document 350002.013.
1.
Unlock the handles
by
inserting a screwdriver into the holes to release the spring mechanism
2.
Insert or remove the rectifier
by
sliding it fully into the power shelf, so that it makes proper contact
or
using both handles to pull the module loose. Support from underneath
before the unit is completely free
3.
Lock the handles
by
pushing the handles up into their housings (locked position). Then, the
rectifier will be securely locked in the shelf, or ready for transport
4.
Mount blind panels
in
unused rectifier locations
Electric
Shock
Handle
in unlocked position
Flatpack2
rectifier
Blind panel’s upper
locking tabs
Screwdriver
to release the
locking tabs
CAUTION:
Do not relocate
already hot-plugged rectifiers
to other positions in the power
shelf.
New rectifiers
must be hot-plugged in the power shelf, one at time, starting from ID
number 1, 2, 3 and so on; refer to page 19.
WARNING:
To replace installed rectifiers with new ones, remove the installed rectifiers and
wait for the controller to notify communication error with the extracted rectifiers. Push the new
rectifiers fully into the power shelf — one module at a time, allowing a 2s delay. Start with the
shelf position with lowest ID number. Lock their handles.
Device
Hazard
!
Opening and Closing
Smartpack2 Master
Controller
Opening the controller’s right side enables inserting an SD card
and temporarily connecting an Ethernet cable.
1.
To open it,
pull the handle’s knob slightly outwards
(use your fingers or a pen) and
2.
then
slide the handle to the left
(the controller’s right side opens)
3.
To close it,
push the controller’s front inwards
Smartpack2 Master
controller (locked)
Handle in locked position
Smartpack2 Master
controller (open)
Handle in open
position
SD card
CAUTION
:
- The rectifiers may be warm, but
do not hand-carry
them by their handles
-
Open the handles before inserting
them into the power shelves (hot-pluggable)
The rectifier incorporates a Mains fuse in each line. Double Pole / Neutral Fusing
Device
Hazard
!