10 .6 .6 Air actuator control
Parameter 48
In cyclic operation, parameters 48 and 49 on BCU..F1, F2 and F3
determine the behaviour of the air actuator during burner start.
Parameter 48 = 0: opens on external activation.
t
SA1
t
Z
04
02
03
00 A0
t
t
FS1
t
SA2
t
FS2
A8
06
07
2
10
∨
53
A
88
ϑ
1
46
1
ϑ
2
4
11
9
5
37-38
13
V1
1
2
14
V2
14
V3
57
V4
17-18
8
M
This setting together with parameter 49 = 0, see page 83
(Air actuator can be activated externally on start-up), is re-
quired for burners on which the air/gas ratio is controlled by
a pneumatic air/gas ratio control system and which need
to be started at low-fire rate, e.g. on two-stage-controlled
burners, see page 10 (Two-stage-controlled main burner
with permanent pilot burner). In this case, activation of the air
actuator during burner start via the input at terminal 2 must
be prevented.
External control allows switchover between low fire and high
fire during operation.
Parameter 48 = 1: opens with gas stage 1.
t
SA1
t
Z
04
02
03
00
A0
t
t
FS1
t
SA2
t
FS2
00
A0
00
A8
A6
A7
2
10
∨
53
A
88
ϑ
1
46
1
ϑ
2
4
11
9
5
37-38
13
V1
1
2
14
V2
14
V3
57
V4
17-18
8
M
The air actuator opens at the same time as safety time t
SA2
begins and the main burner starts.
Parameters > Air control
▼