BCU 580 · Edition 11.15
83
10 .6 .7 Air actuator can be activated externally on start-up
Parameter 49
Parameter 49 = 0: cannot be activated.
02
00
A000
t
SA2
A8
07
04
t
t
FS2
06
88
A
37-38
2
10
43
13
5
V1
1
14
V2
1
46
11
9
8
2
4
42
1
2
t
SA1
t
Z
t
FS1
A000
03
ϑ
1
ϑ
2
∨
53
M
During start-up, the air actuator remains closed. The air actua-
tor cannot be activated externally.
Parameter 49 = 1: can be activated externally.
A2
00
A000
t
SA2
A8
A7
A4
t
t
FS2
A6
88
A
37-38
2
10
43
13
5
V1
1
14
V2
1
46
11
9
8
2
4
42
1
2
t
SA1
t
Z
t
FS1
A000
A3
ϑ
1
ϑ
2
∨
53
M
The air actuator can be activated externally via the input at
terminal 2 during start-up. Parameter 48 must be set to 0 for
this purpose, see also page 80 (Air actuator control).
10 .6 .8 Air actuator in the event of fault
Parameter 50
This parameter decides whether the air actuator can be ac-
tivated externally via the input at terminal 2 in the event of a
fault lock-out.
Parameter 50 = 0: cannot be activated. The air actuator re-
mains closed in the event of a fault lock-out. It cannot be
activated externally via the input at terminal 2.
Parameter 50 = 1: can be activated externally. The air actuator
can be activated externally via the input at terminal 2 during
a fault, e.g. for cooling.
Parameters > Air control