BCU 580 · Edition 11.15
62
10 .3 .3 Burner application
Parameter 78
This parameter enables the BCU to be adjusted to various
burner applications. In addition, an optional pilot gas valve
(V3) can be parameterized via which the burner is started with
a defined ignition capacity.
Parameter 78 = 0: burner 1. Two valves (V1, V2) are included for
the burner. These are connected to the valve outputs (terminals
13 and 14). Valves V1 and V2 are opened in parallel to start
the burner in order to release the gas supply to the burner.
BCU 570
µC
V1
V2
14 15
13
52
55
54
53
56
47 48
58
03
02
01
04
2
1
3
9
14
15
13
5
17-18
t
t
FS1
t
SA1
t
BP
Parameter 78 = 1: burner 1 with pilot gas. Three valves (V1, V2
and V3) are included for a burner with a pilot gas valve. These
are connected to the valve outputs (terminals 13, 14 and 15).
Valves V1 and V3 open to start the burner. The burner is started
with a limited ignition capacity using gas valve V3. After the
elapse of the safety time t
SA1
(program step 02), valve V2 opens.
Valve V3 limits the ignition capacity. After the elapse of the
flame proving period t
FS1
(program step 04), it is closed again.
For this application, it must be ensured that the flame proving
period (P95) is set to a value ≥ 2 s.
BCU 570
µC
V1
V2
V3
14 15
13
52
55
54
53
56
47 48
58
03
02
01
04
2
1
3
9
14
15
13
5
17-18
t
t
FS1
t
SA1
t
BP
Parameters > Behaviour during start-up
▼