Operating & Maintenance Instructions
13
_____________________________________________________________________________________
Count
Reverse run/Power fail
The Reverse Run Count display is shown below (for export meters the display shows the
number of instances the meter has been exporting).
Chevrons Reference
id
4 - Count
1 - Reverse Run (Max 255)
2 - Power Fail (Max 65535)
Hours
The following durations can be displayed:
Time in Rate 1
Time in Rate 2
Total energised time
Cumulative kWh anti-creep time
The format of the display is shown as the number hours (hhhhhh). The total on time of 6852
hours for Rate 2 is shown below.
Chevrons Reference
id
5 - Hours
1 - Time in Rate 1
2 - Time in Rate 2
3 - Total on Time
4 - Cum kWh Anti-creep Hours
Error Codes
Errors are shown in the following format.
Er 00001
Er 00010
Er 00100
Hardware Error
Configuration Checksum Error
Billing Data Checksum Error
The example shows 'Configuration Checksum Error'. If no errors exist, this display is skipped.
The following manufacturing options are available:
1.
Omit the error display from the display sequence if an error occurs
2.
Display or omit the alarm indicator from the display if an error occurs