AHU Electrodes Humidifier - VEH
20.2.EN
12
Elsteam S.r.l - via E. Fermi, 496 - 21042 Caronno Pertusella (va) - Tel.+39 02 9659890 - Fax +39 02 96457007
E-mail: [email protected] - Web: http://www.elsteam.com
10.5
Drain time.
Set the time during which the drain system remains open to allow emptying of the tank. The time
is in seconds, from 1 to 250.
Default 120”.
10.6
Water fill time
Set the time during which the inlet valve is open water. The time is in seconds, from 1 to 250.
Default 10”.
10.7
Purge Time.
Set the purge time during which the drain system remains open to allow a small discharge of
water. The time is in seconds, from 1 to 250.
Default 1”.
10.8
Heating time
Set the waiting time during which the water in the tank is heated by the passage of the current.
The time is in seconds, from 1 to 1200 (= 20min.).
Default 80”.
10.9
TA coefficient.
Set the coefficient for the TA mounted in the humidifier. It is a number from 10 to 9999, modified
in steps of 10.
Default 750.
10.10
Level sensor
Set the type of level sensor connected. Can be chosen among:
•
HV Level switch (High Voltage). Input IN-DIG0
•
Contact with float on input IN-DIG1 (jumper JP2 must be closed):
a.
N.C. = normally closed.
b.
N.O. = normally open.
Default HV Level switch
10.11
Pressure threshold
2000Pa
10.12
Minimum 0-10V Input Calibration
This parameter allows varying the minimum threshold for intervention in the case of using an
external controller with different voltages from 0-10V.
10.13
Water change interval
It indicates the interval between complete changes of water in the kettle.
(Default 4h)