KNX T-UN Temperature Sensor • Date of issue: 31/08/2010 • Technical changes reserved. Errors reserved.
3
The following standards have been considered for the evaluation of the product in terms
of electro magnetic compatibility:
Transient emissions:
•
EN 60730-1:2000 Section EMV (23, 26, H23, H26) (threshold category: B)
•
EN 50090-2-2:1996-11 + A1:2002-01 (threshold category: B)
•
EN 61000-6-3:2001 (threshold category: B)
Interference resistance:
•
EN 60730-1:2000 Section EMV (23, 26, H23, H26)
•
EN 50090-2-2:1996-11 + A1:2002-01
•
EN 61000-6-1:2004
The product has been tested for the above mentioned standards by an accredited EMV
laboratory.
Installation and Commissioning
Installation, inspection, commissioning and troubleshooting
of the sensor must only be carried out by a competent electrician.
Disconnect all lines to be assembled, and take safety precautions against accidental
switch-on.
The sensor is exclusively intended for appropriate use. With each inappropriate change
or non-observance of the instructions for use, any warranty or guarantee claim will be
void.
After unpacking the device, check immediately for any mechanical damages. In case of
transport damage, this must immediately notified to the supplier.
If damaged, the sensor must not be put into
operation.
If an operation without risk may supposedly not be guaranteed, the device must be put
out of operation and be secured against accidental operation.
The sensor must only be operated as stationary system, i.e. only in a fitted state and after
completion of all installation and start-up works, and only in the environment intended
for this purpose.
Elsner Elektronik does not assume any liability for changes in standards after publication
of this instruction manual.
Installation position
The evaluation electronics of KNX T-UN is installed in a socket. When choosing the
installation position avoid direct sun light as this could result in incorrect temperature
measurements.
For indoor installation the measuring sensor should not be mounted above a radiator for
the same reasons. Always ensure that direct draft from windows or doors does not
impair the measured values.