6.3.4. Set time switch event
System > Set automatic > General settings > Time switch event
32 times can be set in the weekly clock, which can be used for temperature regulators.
The time and day of the week are set for each time.
Time switch event:
Displays how many time switches are set. Tap the field to set up the time switches.
Select an event from the list on the right and apply it. If no settings have been made,
the fields show
Time switch event 1...32
. The entered name is shown later.
Enter an
Name
to help you allocate the time switch to the motor or device later.
Select a
Time
.
Select the
Days of the week
, when the time switch is to apply.
6.3.5. Set night back cooling (ventilation)
System > Set automatic > General settings > Night back cooling
Night back cooling via windows and ventilation units is enabled if a set outdoor tem-
perature is exceeded for a longer period.
"Night back cooling" is then displayed on the start page.
7.4. Alarm and error messages > Night back cooling, Page 137
The window(s) and ventilator(s) which are used for the night back cooling, as well as
the time period over which these are activated, can be set in the automatic operation
functions for the individual windows and ventilators.
Night back cooling:
Shows the settings for the night back cooling as soon as the re-cooling has been setup.
Tap the field to apply the configuration.
Switch the night back cooling
On
in order to set up and use for windows / fans.
Use the slider to set how high the
outside temperature
must have been in the last
few hours in order to start the cooling.
Default setting: 16°C.
Set the
duration
, for which the outdoor temperature must have been above the min-
imum temperature (trigger period).
Default setting: 48 hours
Night back cooling is ended when the set outdoor temperature has been undercut by
2°C for a specific period. This period depends on the trigger period set and the duration
of the temperature exceedance. It is a maximum of one third of the set trigger period
(e.g. max. 16 hours for a 48-hour trigger period).