Cala KNX T 201/202 Sunblind push button
1
Cala KNX T 201/202 Sunblind push button
• Version: 04.10.2021 • Technical changes and errors excepted. • Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany • www.elsner-elektronik.de •
Technical Service: +49 (0) 7033 / 30945-250
Cala KNX T 201 Sunblind,
Cala KNX T 202 Sunblind
Temperature Controller,
Button for Shading
Technical specifications and installation instructions
1.
Description
The
Cala KNX T 201/202 Sunblind push button
has touch-sensitive buttons
with which functions can be called up in the KNX building bus system. The glass
surface is printed with areas for setting the temperature and solar protection. Whi-
te LEDs are integrated in these areas and their behaviour can be adjusted.
A temperature sensor is integrated into
Cala KNX T 201/202 Sunblind
. An ex-
ternal temperature reading can be received via the bus and processed with its own
data to create a total temperature (mixed value).
The
Cala KNX T 201/202 Sunblind
has a PI controller for heating and cooling.
The setpoint temperature can be changed using the "+" and "-" touch buttons.
Communication objects can be linked via AND and OR logic gates.
The device is supplemented with a frame of the switch series used in the building,
and thus fits seamlessly into the interior fittings.
Functions:
•
Operating zone for temperature control
with 2 areas (warmer, cooler)
•
LEDs
can be set. All LEDs Off, all LEDs as ambient lighting, all LEDs
individually controllable
•
Area function
when touching two or more push buttons. Can be
configured as switch, selector switch, as 8 or 16 bit encoder or for scenario
recall
•
Temperature
measurements.
Mixed value
from own measured value and
external values (proportion can be set by percentage), output of minimum
and maximum values
•
PI-controller for heating
(one or two-level) and
cooling
(one or two-
level) according to temperature. Regulation according to separate setpoints
or basic setpoint temperature
•
2 AND and 2 OR logic gates
each with 4 inputs. 8 logic inputs (in the form
of communications objects) can be used as inputs for the logic gates. The
output from each gate can be configured optionally as 1-bit or 2 x 8-bit
Additional functions Cala KNX T 201 Sunblind:
•
1 operating zone for blinds
, awnings, shutters or windows with 2 areas
(up/down with short/long distinction)
Additional functions Cala KNX T 202 Sunblind:
•
2 operating zones for blinds
, awnings, shutters or windows with 2 areas
(up/down with short/long distinction)
Configuration is made using the KNX software as of ETS 5. The
product file
can
be downloaded from the ETS online catalogue and the Elsner Elektronik website
on
www.elsner-elektronik.de
in the “Service” menu. There you will also find
the product manual.
1.0.1. Area function
If the area function in ETS has been activated, another function is available along-
side the regular key functions. This is triggered by touching multiple keys, e.g. if
you touch the sensor with the palm of your hand.
Using the area function
If a key is pressed and another (different) key is touched within 0.2 seconds, the ac-
tion set in the ETS is performed for the area operation (See Fig. 1 a) and b)). The
keys are then blocked for 0.5 seconds.
Using the normal key function
If a key is pressed and no other key is touched within 0.2 seconds, the normal key
function is enabled/provided for 5 seconds (See Fig. 1 c) and d)). This is extended
for 5 seconds with each push of the button.
If the area function in the ETS is disabled, the keys can be used normally at any ti-
me.
1.1. Scope of delivery
•
Push button in casing
•
Base plate
Additionally
required (not included in the deliverables):
•
Device socket according to DIN 49073
•
Frame (for insert 55 x 55 mm), compatible to the switch scheme used in the
building
1.2. Technical specifications
The product conforms with the provisions of EU guidelines.
1.2.1. Accuracy of the measurement
Measurement variations from permanent sources of interference (see chapter
Ins-
tallation position
) can be corrected in the ETS in order to ensure the specified ac-
curacy of the sensor (offset).
When
measuring temperature
, the self-heating of the device is compensated.
2.
Installation and commissioning
Installation, testing, operational start-up and troubleshooting should
only be performed by an authorised electrician.
CAUTION!
Live voltage!
There are unprotected live components inside the device.
• Inspect the device for damage before installation. Only put undamaged
devices into operation.
• Comply with the locally applicable directives, regulations and provisions
for electrical installation.
• Immediately take the device or system out of service and secure it against
unintentional switch-on if risk-free operation is no longer guaranteed.
Use the device exclusively for building automation and observe the operating ins-
tructions. Improper use, modifications to the device or failure to observe the ope-
rating instructions will invalidate any warranty or guarantee claims.
Operate the device only as a fixed-site installation, i.e. only in assembled condition
and after conclusion of all installation and operational start-up tasks, and only in
the surroundings designated for it.
Elsner Elektronik is not liable for any changes in norms and standards which may
occur after publication of these operating instructions.
2.1. Installation position
The
Cala KNX T 201/202 Sunblind push button
is installed on a device socket.
May be installed and operated in dry interior rooms only.
When selecting an installation location, ensure that the measurement results are
affected as little as possible by external influences. Possible sources of interference
include:
•
Direct sunlight
•
Drafts from windows and doors
•
Draft from ducts which lead from other rooms or from the outside to the
junction box in which the sensor is mounted
•
Warming or cooling of the building structure on which the sensor is
mounted, e.g. due to sunlight, heating or cold water pipes
•
Connection lines and ducts which lead from warmer or colder areas to the
sensor
Measurement variations from permanent sources of interference can be corrected
in the ETS in order to ensure the specified accuracy of the sensor (offset).
2.2. Composition of the device
2.3. Installation of the sensor
First install the windproof socket with feed line. Seal the inlet tubes as well, in order
to prevent draughts.
Then screw the base plate to the socket and place the switch program frame. Con-
nect the bus cable +/- to the plug (black-red).
Insert the device firmly onto the metal frame using the catches so that the device
and the housing are fixed together.
3.
Commissioning
Never expose the device to water (e.g. rain) or dust. This can damage the electro-
nics. You must not exceed a relative humidity of 95%. Avoid condensation.
After the bus voltage has been applied, the device will enter an initialisation phase
lasting a few seconds. During this phase no information can be received or sent via
the bus.
Cala KNX T 202 Sunblind:
Item numbers
71050 (white),
71052 (black)
Cala KNX T 201 Sunblind:
Item numbers
70990 (white),
70992 (black)
Casing
Genuine glass, plastic
Colours
• similar to RAL 9010 pure white
• similar to RAL 9005 deep black
Installation
on device socket according to DIN 49073
Degree of protection
IP 20
Dimensions
Housing approx. 55 x 55 (W x H, mm),
Installation depth approx. 10 mm,
Base plate approx. 71 x 71 (W x H, mm),
Total weight
approx. 50 g
Ambient temperature
Operating 0…+55°C, storage -30…+85°C
Ambient humidity
5…95% RH, avoid condensation
Operating voltage
KNX bus voltage
Bus current
max. 20 mA
Data output
KNX +/- Bus plug-in terminal
Group addresses
max. 167
Allocations
max. 167
Communication
objects
Cala KNX T 201 Sunblind: 92
Cala KNX T 202 Sunblind: 98
Temperature measu-
rement range
0…+55°C
Temperature resolu-
tion
0.1°C
Key function readiness
Key function readiness
Fig. 1
0s
0.2s
5.2s
Key Y
Key X
Key X
Design
Function Y
Key function readiness
Area function
Examples of normal key functions
0.5 s block
Key X
Design
Area function
Key Y
Design
Function X
a)
b)
c)
d)
Key X
Key Y
0.5 s block
Design
Area function
Area function examples
readiness
Fig. 2: Sectional drawing.
The
Cala KNX T 201/202 Sunblind
push button
fits in a standard connec-
tor socket (Ø 60 mm, depth 42 mm).
The frame is not included in the delive-
ry!
Installation depth
27 mm
Construction depth
10 mm
2
3
1
1
1
1
2
3
3
Cala KNX T 201 Sunblind
Cala KNX T 202 Sunblind
Fig. 3: Front
1 Ventilation slit (top and bottom)
2 „Temperature“ area with 2 touch surfaces and temperature display
3 „Sun protection/drive“ area with 2 touch surfaces per channel
Fig. 4: Back
1 Base frame
2 KNX terminal BUS +/-
3 Programming button (reces-
sed) for teaching the device
4 Programming LED (recessed)
5 Catches
5
1
3
2
4
EN