28
Parameter setting
Weather Station Suntracer KNX sl basic
• Version: 26.08.2021 • Technical changes and errors excepted.
Select whether the minimum and maximum value should be used.
6.4.
Temperature threshold values
Activate the temperature threshold values required (maximum four) The menus for the
further setting of the threshold values are then displayed.
6.4.1. Temperature threshold value 1-4
Threshold value
Set, in which cases threshold values and delay times received are to be kept per object.
The parameter is only taken into consideration if the specification/ setting by object is
activated further down. Please note that the setting "After power restoration and pro-
gramming" should not be used for the initial start-up, as the factory settings are always
used until the first call (setting via objects is ignored).
Select whether the threshold value is to be specified per parameter or via a communi-
cation object.
When the
threshold value per parameter
is specified, then the value is set.
on change of
(if sent on change)
0.1°C • 0.2°C • 0.5°C • 1.0°C • 2.0°C • 5.0°C
Send cycle
(if sent periodically)
5 s … 2 h; 10 s
Use minimum and maximum value
No • Yes
Threshold value 1
No • Yes
Threshold value...
No • Yes
Threshold value 4
No • Yes
Maintain the
threshold values and delays received via
communication objects
• never
• after power supply restoration
• after power supply restoration and pro-
gramming
Threshold value setpoint using
Parameter • Communications object
Threshold value in 0.1°C
-300 … 800; 200