18
Value of the blocking object
before 1. communication
0 • 1
Send actuating variables
• on change
• on change and periodically
Transmission cycle
(only if sending „periodically“)
5 s … 2 h
Status object/s send
• on change
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically
Transmission cycle
(only if sending „periodically“)
5 s … 2 h
Controller target value:
……………………………
Target value setpoint per
Parameter • Communication object
If the target value is set per Parameter:
Target value setpoint per
Parameter
Target value in 0.1°C
-300 … 800
If the target value is set per Communication object:
Target value setpoint per
Communication object
The value communicated last shall be
maintained
• not
• after restoration of voltage
• after restoration of voltage and programming
(Do not use for first commissioning)
Start target value in 0.1°C
valid until 1.communication
(only if the value communicated last is “not”
maintained or “after restoration of voltage”)
-300 … 800
Limitation of object value (min) in 0.1°C
-300 … 800
Limitation of object value (max) in 0.1°C
-300 … 800
Type of the target value change
• Absolute value
• Increment/decrement
Step size
(only with “Increment/decrement”)
0.1°C • 0.2°C • 0.3°C • 0.4°C • 0.5°C • 1°C • 2°C •
3°C • 4°C • 5°C