Parameter setting
Sensors Intra-Sewi KNX T and Intra-Sewi KNX TH
• Version: 11.06.2018 • Technical changes and errors excepted.
Block
The switching output can be blocked using an object.
If the block is activated, define specifications here for the behaviour of the output when
blocked.
The behaviour of the switching output on release is dependent on the value of the pa-
rameter "Switching output sends" (see "Switching output")
5.5.2. Heating control level 1/2
If a heating control mode is configured, one or two setting sections for the heating le-
vels are displayed.
In the 1st level, heating is controlled by a PI control, which allows to either enter control
parameters or select predetermined applications.
In the 2nd level (therefore only in case of 2-level heating), heating is controlled via a PI
or a 2-point-control.
Use switching output block
No • Yes
Analysis of the blocking object
• At value 1: block | At value 0: release
• At value 0: block | At value 1: release
Blocking object value before
1st communication
0 • 1
Behaviour of the switching output
On block
• Do not send message
• send 0
• send 1
On release
(with 2 seconds release delay)
[Dependent on the "Switching output
sends" setting]
Switching output sends on change
• Do not send message
• Send switching output status
Switching output sends on change to 1
• Do not send message
• if switching output = 1
send 1
Switching output sends on change to 0
• Do not send message
• if switching output = 0
send 0
Switching output sends on change and
periodically
Send switching output status
Switching output sends on change to 1
and periodically
if switching output = 1
send 1
Switching output sends on change to 0
and periodically
if switching output = 0
send 0