26
Parameter setting
Actuator KNX S1R-BA4-UP 24 V
• Version: 27.05.2020 • Technical changes and errors excepted.
Use movement limit 1/2:
The movement limits are activated here, and can them be configured in their own
menu items. See ‘Movement limits’ on Page 30.
Short time restriction (for blinds):
If short time restriction is active, only short time movement commands are still
possible manually. If the function "Allow step commands only for blind adjustment" is
activated simultaneously, (see
, page 21) only the slats can
still be adjusted by hand but no longer the movement position of the shutter.
Restriction is active for object value 1.
Automatic reset:
With the manual operation the automatic of the drive is deactivated. Here it is set when
the automatic is reactivated.
Use Block 5 (low priority)
• no
• yes, with blocking object
• yes, as wind blocking
• yes, as rain blocking
Priority is
• Block 5 over Manual
• Manual over Block 5
Use monitoring of blocking objects
No • Yes
Monitoring period for blocking objects
(only if using monitoring of the blocking
objects)
5s... • 2 h; 5 min
Behaviour if a blocking object is not
received
(only if blocking object monitoring is used)
• Stop
• Up command • Down command
(Shutters/roller blinds)
• On command • Off command
(Awnings)
• Close command • Open command
(Windows)
Use short time limit
no • yes
Value of the object in front of 1.
communication and bus voltage
restoration
(if short time restriction is used)
0 • 1
Manual switches to automatic after
• expiry of a waiting period
• reception of an object
• expiration of a waiting period or receipt of
an object
Waiting period in min
(if "Expiration of a waiting period" was
chosen)
1...255; 20
Switch to automatic for an object value
(if "Receipt of an object" was chosen)
0 • 1 • 0 or 1