background image

15

Device alarm functions

Smoke alarm Salva KNX

 • Version: 30.01.2017 • Technical Changes and Errors excepted.

Alarm memory active 
(i.e. there was an alarm 
state during the previous 
24 hours)

No sound

Flashes 3 times every 43 
seconds

Function test

Loud interval tone

Flashing twice per second
while the light transmis-
sion bar 
is pressed

Function / meaning

Signal tone

Red LED

Summary of Contents for 70405

Page 1: ... Item numbers 70405 Salva KNX basic 70406 Salva KNX TH Elsner Elektronik GmbH Control and Automation Engineering Sohlengrund 16 75395 Ostelsheim Phone 49 0 70 33 30 945 0 info elsner elektronik de Germany Fax 49 0 70 33 30 945 20 www elsner elektronik de EN Technical Service 49 0 70 33 30 945 250 ...

Page 2: ...g on temperature and for ventilation depending on humidity Functions Smoke alarm sensors with optical detection based on the scattered light principle certified according to EN 14604 2005 AC 2008 and 1172 CPR 150013 Local acoustic alarm signal output warning sound at least 85 dB and transfer to KNX bus Local alarm acknowledgement Signalling of smoke alarm Smoke chamber pollution measurement and po...

Page 3: ... with skirting 9 V battery 2 screws and dowels for assembly always use fastening material that is suitable for the material underneath 1 1 Technical specifications Housing ABS glass Colour White Translucent Assembly Surface mount Protection category IP 30 Dimensions Ø approx 113 mm height approx 58 mm Weight approx 280 g Ambient temperature Operation 10 60 C storage 10 C 60 C Surrounding air humid...

Page 4: ...rior temperature measured value increasingly approaches the actual room temperature 2 Installation and commissioning 2 1 Installation notes Installation testing operational start up and troubleshooting should only be performed by an electrician CAUTION Live voltage There are unprotected live components inside the device National legal regulations are to be followed Ensure that all lines to be asse...

Page 5: ...ication of these operating instructions 2 2 Installation location 2 2 1 Equipping the building with smoke alarms The minimum protection is the installation of smoke alarms in the bedrooms and halls and or corridors to ensure that you are woken up during the night in case of a smoke alarm If the building has several floors at least one smoke alarm should be installed in the hall on every floor Plea...

Page 6: ...peratures of less than 10 C or more than 50 C Avoid condensation Do not install in rooms in which a high degree of water vapour is produced under normal circumstances e g kitchen bathroom toilet Do not install near places of fire or open fireplaces Do not install near ventilation shafts e g of air conditioning or circulating air systems Attach the first alarm at a maximum distance of 7 50 m to the...

Page 7: ...cture on which the sensor is mounted e g due to sunlight heating or cold water pipes Connection lines which lead from warmer or colder areas to the sensor Temperature variations from such sources of interference must be corrected in the ETS in order to ensure the specified accuracy of the sensor temperature offset 2 3 Device design 2 3 1 Exterior view 2 Fig 2 1 Skirting 2 Housing with electronics ...

Page 8: ...f the housing 2 Fig 3 1 Battery assembly lock the housing cannot be closed without a battery 2 Fastening opening with 1 screw 3 Openings for fastenings with 2 screws distance 67 mm 4 Opening for bus cable 3 4 1 2 Fig 4 1 Battery 2 KNX terminal 3 LED programming 4 Programming key recessed for bus addressing see Addressing the equipment page 11 3 4 1 ...

Page 9: ...t is not fastened properly Observe the carrying capacity of the wall ceiling material when selecting the place of installation Use fixing materials that are suitable for the material underneath If you are using the screws and dowels provided use a 6mm drill to drill holes with a distance of 67 mm if you are using two screws for installation Use the skirting of the smoke alarm as a stencil Insert t...

Page 10: ...ger of explosion in case of improper handling of the battery Property damage by battery leakage Do not recharge batteries Do not short circuit batteries Do not force batteries open or damage them Do not bring batteries in contact with fire water or high temperatures ATTENTION Do not use rechargeable batteries or mains units for voltage supply In case of mains voltage the device would be out of ord...

Page 11: ...se 4 Maintenance In some German federal states the owner of houses and flats are responsible for the installation and functioning of smoke alarms according to LBO State construction laws see www rauchmelder lebensretter de Maintenance has to be conducted at least annually and according to DIN 14676 includes a visual inspection a function test and if required a battery change A function test also h...

Page 12: ... is damaged 2 Conducting a function test If the function test is successful a signal tone sounds The smoke alarm works proper ly If there is no signal tone the device is not functioning In this case replace the bat tery and conduct the function test again If there is still no signal tone the device is de fect and must be replaced Smoke alarms must be replaced with new devices after a maximum perio...

Page 13: ... not short circuit them Do not force batteries open or damage them and do not bring them into contact with fire water or high temperatures The used battery and the device must be disposed of properly so that valuable resources may be recycled Neither the battery nor the device may be disposed of together with domestic or company waste Approved battery type FDK CP V9Ju Only use lithium batteries Av...

Page 14: ...ashes 3 times every 43 seconds The alarm memory can be reset by pressing the light trans mission bar red LED once 5 3 Operating and alarm signals Function meaning Signal tone Red LED Normal operating mode automatic self test No sound Flashes every 40 seconds Alarm status Loud interval tone in 0 5 second rhythm Flashing twice per second Fault dirt Short signal tone 3 times every 40 seconds LED off ...

Page 15: ...es and Errors excepted Alarm memory active i e there was an alarm state during the previous 24 hours No sound Flashes 3 times every 43 seconds Function test Loud interval tone Flashing twice per second while the light transmis sion bar is pressed Function meaning Signal tone Red LED ...

Reviews: