Description

Ventilation Unit WL800

 • Version: 28.04.2016 • Errors and technical modifications subject to change without notice.

1.0.1. Scope of delivery

Mounting panel with ventilation unit and 10 m connection cable for voltage 
supply

1.1. Technical specification

The product is compliant with the provisions of EU guidelines.

1.1.1. Air intake opening

Sufficient sizing of the air intake opening is an important functional and comfort factor
when utilizing motorised ventilation units. If the air intake opening size falls below the
minimal size (18,360 mm² or approx. 184 cm²), reduced air performance as well as
draught and flow noises can be the result. Comfortable ventilation is achieved with an
opening size starting at 38,400 mm² (384 cm²) for each WL800.

Voltage

230 VAC, 50 Hz

Cable length 
Voltage Supply

10 m 

Power consumption in 
exhaust mode

minimal speed: approx. 8 W
maximal speed: approx. 124 W

Radio frequency

868.2 MHz

Net air output

Exhaust air: max. approx. 555 m³/h, 
Circulation air: max. approx. 163 m³/h
(For exact measuring criteria please inquire at Elsner 
Elektronik)

Required air intake opening   

minimum 18,360 mm² (approx. 184 cm²)
Please observe the instructions in chapter 

Air intake 

opening

, page 3

Sound pressure
at a distance of 3 m

Exhaust mode: 
approx. 37.2 dB(A) at medium speed
approx. 47.0 dB(A) at maximum speed
Circulation mode: 
approx. 41.3 dB(A) at medium speed
approx. 54.1 dB(A) at maximum speed

Heat transition coefficient

0.9 W/m²K (Fan including standard panel)

Panel insulation density

60 kg

Panel compressive strength

350 kPa

Inclination 
for mounting

0° (flat roof) to 90° (wall mounting)
• In case of wall mounting (from 70° to 90°), the addi-

tional option "wall device" must be ordered (sur-
charge).

• In case of flat roof mounting, water on the panel must 

not exceed the height of 2 cm.

Summary of Contents for 60461-60466

Page 1: ...stallation instructions Item numbers 60461 60466 60471 60476 EN Technical support 49 0 70 33 30 945 250 Elsner Elektronik GmbH Control and Automation Engineering Sohlengrund 16 75395 Ostelsheim Phone 49 0 70 33 30 945 0 info elsner elektronik de Germany Fax 49 0 70 33 30 945 20 www elsner elektronik de ...

Page 2: ...nits WS1 WS1000 Warm air from the ridge area is distributed throughout the whole room by the ventilation unit Air circulation to reduce condensation water Automatic function of control units WS1 WS1000 Using a special calculating process the control units recognize critical conditions of temperature and dew point and start the ventilation unit usually even before any moisture starts settling Wirel...

Page 3: ...oltage Supply 10 m Power consumption in exhaust mode minimal speed approx 8 W maximal speed approx 124 W Radio frequency 868 2 MHz Net air output Exhaust air max approx 555 m h Circulation air max approx 163 m h For exact measuring criteria please inquire at Elsner Elektronik Required air intake opening minimum 18 360 mm approx 184 cm Please observe the instructions in chapter Air intake opening p...

Page 4: ... The tolerance for panel width and length for standard and custom sizes is 3 mm Minimum panel sizes at shortening or custom panel Requirement Ventilator combination Note Minimum 1 WL Z per 1 WL800 Air performance is achieved Draught may occur depending on building situa tion and utilization Comfort 2 WL Z per 1 WL800 Ventilator height Outside approx 150 mm Inside approx 165 mm at panel thickness o...

Page 5: ...tions due to technical reasons are possible Due to the different nature of the surface of the panel and ventilator housing slightly different degrees of lustre can occur 2 Installation and start up 2 1 Installation notes Installation testing operational start up and troubleshooting should only be performed by an electrician DANGER Risk to life from live voltage mains voltage There are unprotected ...

Page 6: ...nteed The range of wireless control will be limited by legal reg ulation and structural circumstances Avoid sources of interference and obstacles be tween receiver and transmitter that could disturb the wireless communication Those would be for example Walls and ceilings especially concrete and solar protection glazing Metal surfaces next to the wireless participants e g aluminium construction of ...

Page 7: ...90 the additional option wall device must be ordered surcharge In case of mounting on a flat roof water on the panel must not exceed the height of 2 cm The air outlet must face the direction that is opposite to the weather side Leave sufficient distance to walls or ledges when installing the fan so that the blower unit can be easily removed for disassembly Keep a distance of at least 60mm to the w...

Page 8: ...the ventilation unit for servicing Keep a distance of at least 60mm between the internal hood and the wall Fig 4 Leave sufficient room for disassembly of the blower unit The blower unit is 340mm in length Fig 5 To remove blower unit for servicing 1 Remove the screws on the internal hood and pull the hood down on the air discharge side 2 Shift the hood approx 60mm and remove it Internal hood at lea...

Page 9: ...atically The building control system will display Device has been taught The fan will stop sending Learn telegrams once the reply taught for a learning pro cess or a control command in the event of a power failure during operation is re ceived from a control unit 4 Maintenance The function of the unit should be checked by the specialized dealer installation tech nician once a year and the ventilat...

Page 10: ...hout notice Each time the OFF state is reached the speed change stops automatically so that a direct change between exhaust and circulation modes is impossible Fan OFF stopped flap closed Circulation air mode Press Increase speed Lower rotation speed to OFF Fan OFF Press Exhaust air mode Lower rotation speed to OFF Increase speed Fan OFF ...

Reviews: