IOMOD 16DI

 

4/14/2017 

 

V1.1 | ELSETA | IOMOD 16DI inputs

   

11 

 

User can setup inputs to be driven by 0V (Active low) signal (see Fig. 5.3). With this configuration, user 
will see inputs connected to 0V as “high” or state “1”, input status LED will glow. 

 

 

 

Fig. 5.3 

 
 

 

Summary of Contents for IOMOD 16DI

Page 1: ...ELSETA IOMOD 16DI User manual Elseta 4 14 2017 V1 1...

Page 2: ...acturer L Zamenhofo st 5 LT Vilnius Lithuania We claim that The device IOMOD 16DI Conforms to the following standards EMC Radiation EN 55022 Class A 1 emitted radiation 30 1000MHz Second radiation con...

Page 3: ...rmed by a qualified professional If the safety notes in this manual the term refers to persons qualified specialists authorized to perform commissioning grounding and labeling devices systems and circ...

Page 4: ...MODBUS working information 5 Supported MODBUS functions 6 Modbus registers 6 Testing With THE VINCI software 6 4 Technical information 8 5 Mounting and installation guide 9 a IOMOD 16DI RS485 interfa...

Page 5: ...r Requirements 12 24 VDC 3 Device working information IOMOD 16DI uses Modbus RTU or IEC 60870 5 103 protocol over RS485 interface Protocol used by device can be changed by uploading corresponding firm...

Page 6: ...ed integer in seconds 06 0x06 Preset Single Register Sets single register Register addresses is identical to Read Input Registers addresses Modbus registers Function Register Name Description Values r...

Page 7: ...IOMOD 16DI 4 14 2017 V1 1 ELSETA MODBUS working information 7 Fig 3 1...

Page 8: ...Working environment Indoors 4 Working temperature 30 70 C 5 Recommended operating conditions 5 60 C and 20 80 RH 6 Configuration USB 7 Firmware upgrade USB mass storage device Electrical specification...

Page 9: ...enabled or disabled over USB configuration It is recommended to use termination at each end of the RS485 cable See typical connection diagram on Fig 5 1 Fig 5 1 IOMOD 16DI has 1 8 Unit load receiver w...

Page 10: ...16DI inputs b IOMOD 16DI inputs Typical application of IOMOD 16DI inputs is shown on Fig 5 2 When default configuration for inputs is applied user will see inputs connected to 12 24V as high or state...

Page 11: ...V1 1 ELSETA IOMOD 16DI inputs 11 User can setup inputs to be driven by 0V Active low signal see Fig 5 3 With this configuration user will see inputs connected to 0V as high or state 1 input status LE...

Page 12: ...ould result in Device driver software was not successfully installed error Fig 6 1 User then manually installs drivers by selecting downloaded driver folder Go to Control Panel Device Manager Select f...

Page 13: ...to send return symbol after each command When connected user should immediately see main screen Fig 6 4 Navigation is performed by sending number to terminal User then proceeds by following further on...

Page 14: ...conds default 100 6 Input counter restart Restarts all input counter registers to 0 1 to confirm 0 to cancel 7 Set Default Settings Sets Default Settings 1 to confirm 0 to cancel 8 Firmware Upgrade Ma...

Page 15: ...e screen by pressing 4 Confirm update by pressing 1 Device now enters Firmware Upgrade mode It is recommended to close terminal window when entered firmware upgrade mode Device reconnects as mass stor...

Page 16: ...equipment manufacturer 7 Information of the equipment manufacturer Office address L Zamenhofo st 5 LT 06332 Vilnius Lithuania Tel 370 5 2742707 370 5 2032302 Fax 370 5 2058584 Email support elseta co...

Page 17: ...2015 12 15 L S First version v0 8 2016 05 10 L S Major update Added IEC 103 Description V0 9 2017 01 13 L S Minor updates Added protocol simulator description V0 99 2017 03 22 J S Added connection dia...

Reviews: