ELREHA TKC 19130 Technical Manual Download Page 13

Technical Manual Cold Storage Controllers TKP / TKC x130 - x140

Page  13

  Intelligent Defrost (adaptive defrost) for walk-ins 

(TKP/TKC x140 only)

Main Characteristics

This defrost control method, developed in co-

operation with the ‘

GÜNTNER

’ company, fits 

especially for 

cold stores

 and freezers which 

are closed (like walk-ins), but it is 

less efficient

 in 

applications where the limitation sensor is located 

in the airflow (e.g. open chest freezers).

This  technique 

reduces  significantly  the 

amount  of  energy 

the  refrigeration  plant 

needs.

Especially while 

difficult situations

 (like high 

air-humidity, in cool-down chambers, while long 

opening times of the door of the cold storage 

room, uneven feeding of the cold storage room, 

etc.) the adaptive method protects the evaporator 

from glaciation safely.

Dynamic ‘room-feeding’ situations engage 

the  controller  to  adapt  itself  to  the  new 

situation, without expensive adjustment by 

technical personnel.
Specialized  sensors  or  additional  probes 

are not required.

Parameterisation is very easy:

•   set parameter „

defrost mode

“ (defrost    

  page) to „adaptive“

•   set parameter „

max time to defr

“ (defrost  

  page) to a value which is 2 or 3 times the  

  normal defrost interval. Within this period  

  the device decides  independently about the  

  point in time to defrost.

•  parameter „

time to defr

“ (defrost page)    

  shows the time up to the next defrost.

•  parameters „

pulse defr limit

“ and „

defr    

  temp limit

“ define the range within the    

  heater will be pulsed.

•  set parameter „

defrost forerun

“ to  

 

  several minutes, so the fan will be  

 

  started before defrost heater starts.

•   set parameter „

fan off delay

“ (setpoint    

  page) to the time that the fan will continue  

  running after cut-off of the cooling relay.

 Process Sequence

1

. In the time period set by „

max time to    

  defr

“ the controller decides itself if and at   

  which moment a defrost cycle is necessary.  

  If icing is detected, the controller prepares  

  defrost and begins either immediately or at  

  the next allowed defrost time.

2.

 The fan runs while cooling is stopped and  

  while the defrost heater is not yet switched on

3.

 The fan stops and the heater starts

4.

 Each evaporator is individually heated. 

  The 

leading evaporator

 will be recognized  

  automatically.

5

. With working temperatures of [se  

  hysteresis >= 2,5°C] the controller is able to 

  save energy by increases using of the fan 

  (

more circulating air

). 

6.

 When the „

pulse defrost limit

“ is achieved,  

  the heater will be switched off/on in calculated  

  periods (optimal heat distribution).

7.

 Defrost heater cut off, limit temp. is reached.

8.

 Cooling and fan remain still off (drain time).

9.

 Cooling starts, fan still off. 

10.

 After end of „

fan start delay

“ the fan  

 

  restarts and normal refrigeration goes on.

Refrigeration

Even during normal operation the fan stays on after 

cut-off of cooling to reduce icing.

Recognition of icing

The more ice on the fins the more increases the 

difference of temperature between the room sensor 

and the evaporator sensor. The controller uses the 

value of these sensors, their difference, the historic 

curves of these values as well as curves and duration 

of the past defrostings to calculate the necessity of 

defrosting.

Use of latent energy by airflow

We recommend to use „

defrost forerun

“ (defrost page) 

to switch on the fan several minutes ahead the defrost 

cycle, while cooling stops and the heater is not yet on. 

Additionally, the fan is switched on automatically at a 

certain difference between the sensors. By this, the 

„cooling-energy“ is brought out of the evaporator and 

stored in the chamber. This helps also to reduce the 

amount of heat energy necessary to defrost.

Defrost start

If all six parameters „

defrost time ..

“ are set to Off, the 

controller decides itself when it starts defrost.

● 

Further time influence

   If you want to prevent that defrost starts at  

  certain day-times use all the „

defrost time..

“  

  parameters and set them to points in time  

  where defrost is allowed. If no icing is    

  detected, these times will be ignored. 

  On the other hand, once icing detected, the  

  controller will wait for the next „

defrost time

“  

  before starting defrost.

● 

External command

  Assign one of the digital inputs to „

manual  

  defrost

“. By applying voltage to that input it is 

  possible to start defrosting at every moment.

Defrost heater

After the end of the "Fan OFF Delay", the defrost 

heater switches on up to the temperatur has been 

readed the value „

pulse defrost limit

“. The heat energy 

of the heater will dissipate slowly and melt the ice. 

The length of the cut-off is calculated by the controller 

and as soon as some criteria are fulfilled, it will switch 

on the heater again. The heater will be pulsed until 

the temperature of the evaporator sensor reaches 

the value of „

defrost temp. limit

“. 

This procedure fits in the same way for the case of 

several evaporators in the chamber.

By this way a defrost period will take longer, 

but will be more efficient.

Special mode for roomtemperatures > 2,5°C

Evaporators can be de-iced already at temperatures 

from 2°C by forced air. When cooling stops, fans are 

turning on until ice and frost are melted. 

Thus humidity stays in the chamber which will improve 

the quality of certain goods like meat or vegetables. 

Additonally to the compulsatory "

fan off delay

" (fan is 

forced to continue turning after cooling reached the 

setpoint and stopped), the fan will turn from a specific 

temperature [se hysteresis =>  +2,5°C] until the 

evaporator sensor has reached a certain value.

●  At room temperatures [shysteresis =>   

  +2,5°C] notify to set parameter „

max time to  

  defr

“ to a higher value, because a defrost start  

  is forced if this time is past.

Several evaporators in one chamber

For  certain  plants  it  is  necessary  to  use  several 

evaporators in one chamber. The controller is able 

to control up to 4 evaporators in one chamber. Even 

in  this  case  one  unique  roomsensor  is  sufficient. 

E.g.  for  a  chamber  with  3  evaporators  you  need 

only 4 sensors:

●  one controlsensor

●  three defrost sensors (one for each evaporator)

If a defrost cycle is necessary, all evaporators will 

start defrost at the same time to avoid short circuit 

of air, when one is heating and the fan of the other 

is turning. So the one with the highest rate of icing 

determines the start of the defrost cycle. 

The controller is able to 

determine just this evapo-

rator 

and even to adapt it when conditions change.  

Thus always the evaporator with the most ice initiates 

defrost start, nevertheless the quantity of energy 

which is necessary to defrost will be calculated for 

each evaporator separately. 

To  finish  defrost  cycle  all  evaporators  must  have 

reached the defrost limitation temperature.

Emergency operation in case of bad conditions

In case recognizing extreme conditions, e.g.:

●  charge of unusual very humid goods

●  freezer door was open a very long time

●  the evaporator is sprinkled with water

●  sensor broken or shortened

the emergency operation starts.

To detect malfunction of the defrost control the unit 

uses the increasing of "

max. defrost time

".

If a defrost cycle is terminated by this time, the con-

troller starts several defrosts with the interval which 

corresponds to one quarter (¼) of the time which is 

programmed by „

max time to defr

“.

Therefore  be  careful  in  choosing  the  time  for 

this parameter.

After the end of the disturbance the controller works 

on normally.

Example

 

  Max time to defrost is set to 24 hours. If defrost  

  is not terminated by the evaporator sensor, the  

  controller will start defrost cycle every 24 / 4 = 6  

  hours until a cycle will be finished by the   

  evaporator sensor and not by timer.

  Independent from this procedure, a failure  

  message will be initiated.

End of defrost

When the defrost sensor has reached the defrost 

limitation temperature, the heater stops and the con-

troller waits until "

pause after defrost

" has expired, to 

allow the melted water to flow to the drainage. Then 

cooling starts now, but the fans still stay OFF until the 

"

fan start delay

" has expired to allow the evaporator 

to cool down and to prevent that the fans blow warm 

and humid air or water drops into the chamber.

Summary of Contents for TKC 19130

Page 1: ... defrost act fail page 20 02 18 11 492 actual values 20 02 18 11 49 setpoint page 20 02 18 11 49 defrost page 20 02 18 11 49 mode page 20 02 18 11 49 assignment page 20 02 18 11 49 hist fail page 20 02 18 11 49 ESC RET RET RET RET RET RET RET current failure etc last failure 1 etc sensor 1 etc setpoint level X etc defrost mode etc configuration TKP TKC Test 20 02 18 11 49 RET User Code date time e...

Page 2: ...ge caused by failure to comply with these operating instructions Nor will ELREHA be held liable for any personal injury or damage to property caused by improper handling or failure to observe the safety instructions and recommendations contained in this or any other ELREHA supplied document related to this product Thismanualcontainsadditionalsafetyinstructionsthroughout the functional description ...

Page 3: ...tethe StandardDisplay aftersomeseconds incaseofafailureitwilldisplaytheactualfailure factory set is the actual value of probe 1 This will also displayed if you have selected any parameterandyouhaven ttouchabuttonformore than 3 minutes If you think that it is suggestive to show any sensor value as permanent parameter do the following Change permanent parameter Select the parameter you want to have ...

Page 4: ...2 h m s resettable only 00 00 00 up to runtime relay 6 2 00 00 00 analog value X 1 output is X of the selected range OC1 OC2 OC3 OC4 X 1 voltage at this digital inputs relay status X 1 state of relays 1 6 1 ON avtivated 0 OFF de activated Setpoint Page Level Range Factory setting setpoint layer 1 1 2 1 setpoint Ch 1 1 50 50 C 20 C setpoint Ch 2 1 50 50 C 20 C setpoint Ch 3 1 50 50 C 20 C setpoint ...

Page 5: ...0 60 00 mm ss 15 00 mm ss frame pulse day 2 0 100 100 frame pulse nigt 2 0 100 100 frame pulse act X display of the actual frame pulse duration evtl shifted by the VPR system alm temp low 2 yes no yes night setp ON 2 0 00 thru 23 59 off off night setp OFF 2 0 00 thru 23 59 off off runtime mess at 2 0 23 h off 6 h corr sensor 1 2 calibration offset adjustable 10 actual value also adjustable K 0 up ...

Page 6: ...ly sens funct sensor 1b 3 dto alarm sensor 1 funct sensor 1c 3 dto weighting 1 3 0 100 weighting for the virtual sensor 0 funct sensor 2a 3 dto defr sens 1 1 funct sensor 2b 3 dto funct sensor 2c 3 dto weighting 2 3 0 100 weighting for the virtual sensor 0 funct sensor 3a 3 dto control sens 2 funct sensor 3b 3 dto alarm sensor 2 funct sensor 3c 3 dto weighting 3 3 0 100 weighting for the virtual s...

Page 7: ... OC3 OC4 8 31 95 3 74 89 5 3 52 3 4 E LR E H A RET 2 1 ESC 7 8 6 5 95 3 74 133 5 24 32 30 10 12 14 16 18 20 22 24 26 28 2 4 6 8 z d d z 32 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 Analog PCB Supply PCB 129 5 08 ELREHA 4 1 3 2 1 3 2 ESC RET 70 8 2 76 TKC 19 RS 485 4 L 3 2 1 N 7 6 5 TKP 31xx 11 10 9 8 14 13 12 inter com 35 34 33 AC DC 42 41 40 39 38 37 36 RS 485 OUT DO NDO RS 232 DO IN GND 18 15 17 ...

Page 8: ...unit changes to the Customer Level if no key is pressed for about 3 minutes Parameter Protection Identificaton Almost all parameters except the temperature setpoints are protected by a simple password If you have to change a parameter and you have pressed the RET key this display appears The controller expects now the input of a code no This code no Code 1 is related from the actual time of the da...

Page 9: ... will switch off This value is the threshold for the undertemperature alarm at the same time Theundertemperaturelimitationcannot be switched off and is also active with disabled low temperature warning Refrigeration delay after power up The start of refrigeration after power up resp mains loss can be delayed by parameter re frDlyAftMnsOff Setpoint Page In plants with many cold storages this functi...

Page 10: ... Circuit Off Each digital input can be configured to switch off one oremorecoolingcircuits circuitOFFX Ifactivated all regulation and control functions and temperature alarmsoftheconcernedcircuitsaredisabled Never thelesstheothersarestillworking Thisismemorized in the list of the historical failures Relay function unit on The function unit on assigned to an output relay has the effect that this re...

Page 11: ...milar act img 0 10V The outputs provide an image of the value of refrig sensor 1 voltage 50 C 0V 100 C 10V current 50 C 0mA 100 C 20mA act img 4 20mA The outputs provide an image of the value of refrig sensor 1 voltage 50 C 2V 100 C 10V current 50 C 4mA 100 C 20mA Control with the analog output signal PI con trol PID T1 0 10V This PID controller with 0 10V DC signal is assigned to cooling circuit ...

Page 12: ...the temperature in the evaporator reaches the limitation setpoint In case of bad working conditions like to many ice or a defect defrost heater defrost is ter minated by max defr time If the number of defrost periods terminated by timer exceeds the number programmed by parameter n o def evnt alm a failure will be indicated In case of defrost by airflow without evapo rator sensor this function has ...

Page 13: ...detected these times will be ignored On the other hand once icing detected the controller will wait for the next defrost time before starting defrost External command Assign one of the digital inputs to manual defrost By applying voltage to that input it is possible to start defrosting at every moment Defrost heater After the end of the Fan OFF Delay the defrost heater switches on up to the temper...

Page 14: ...s voltage fan operation is set to permanent defrost type is set to on and pause aft defr is set to 0 2 fan in interval mode defrost by fan In use for cold storage chambers with higher temperatures Use a relay output for the fan In this case you select fan operation inter val and defrost type on 3 fan in interval mode defrost by electric heater hot gaz In use for cold storage chambers with lower te...

Page 15: ...he information about the market temperatureandtheairhumidityisdeliveredfrom a host system VPR 52xx to allow the controller to calculate the absolute humidity Limits Temperature 19 24 C Humidity 40 70 r H At the upper limits the frequency ratio is equiva lent to the values set by frame period and frame pulse at the lower limit the pulse width will be reduced by half frame period frame pulse ON OFF ...

Page 16: ...problem is solved To see if this function is released look at solenoid valve actual values page Data transmission disturbances If the controller gets no new information from the VPR it continues working with the actual settings If there was an order from the VPR to close the solenoidvalvesandatechnicaldefectinteruptsthe datatransmissionformorethan30minutes theTKx ignores this order and starts work...

Page 17: ... this purpose If the evapo rator has not such a tube assemble it between the fins in the upper part and assure a good thermal exchange It should be placed at the position where the icing stays the longest time while defrosting This depends of type and manufactureroftheevaporator souse your experience Makesurethatthesensordoesn ttouch the heater or any piping with hot gas defrost it must have some ...

Page 18: ...d for the conformity testing to meet the requirements of EMC and Low Voltage Guidelines EN 55011 2016 A1 2017 EN 61010 1 2010 EN 61326 1 2013 CE marking of year 2018 This statement is made for the manufacturer importer by ELREHA Elektronische Regelungen GmbH Werner Roemer Technical Director D 68766 Hockenheim www elreha de Hockenheim 2018 05 24 Name Address City Date Signature EC Declaration of Co...

Reviews: