background image

Page 2   

TAA 2130, TAA 212130

We state the following: When operated in accordance with the technical manual, the criteria have been met that are outlined in the guidelines of the 

council for alignment of statutory orders of the member states on EMC-Directive (2004/108/EC) and the Low Voltage Directive (LVD 2006/95/EC). 

This declarations are valid for those products covered by the technical manual which itself is part of the declaration. To meet the requirements, the 

currently valid versions of the relevant standards have been used
This statement is made from the manufacturer / importer 

by: 

ELREHA Elektronische Regelungen GmbH 

Werner Roemer, Technischer Leiter, 

Technical Director 

D-68766 Hockenheim 

 

 

 

 

 

 

www.elreha.de   

Hockenheim

.............

15.04.2009

.......................................................

(Name / Anschrift /

 name / adress

Ort/

city 

Datum/

date

 

 

Unterschrift/

sign

EG-Statement of Conformity

original set up:  14.4.09, tkd/jr 

checked: 15.4.09, ek/ha  

approved:  15.4.09, mkt/sha 

transl.(E):  

korr: 3.9.15, tkd/jr

Parameterliste
Nr. 

Parameter 

Bereich 

Werkseinst.    

P01

  .... Istwert Fühlereingang 1 ......................... -60,0...110,0°C (-60,0...+310,0°C mit TF 5x1) .......................................................--   

P02

  .... Istwert Fühlereingang 2 ......................... -60,0...110,0°C (-60,0...+310,0°C mit TF 5x1) .......................................................--   

P03

  .... Art der angeschlossenen Fühler ............ 0=TF 201/°C, 1=TF 201/°F, 2=TF 202/°C, 3=TF 202/°F  .......................................0

 

 

4=TF 501/°C, 5=TF 501/°F 

 

P04

  .... Display Modus ....................................... 0=normale Anzeige ................................................................................................0

 

 

1=alle 16 Sekunden wird von P01-Anzeige auf P02-Anzeige gewechselt. 

 

 

Dazu wird jeweils kurz die Parameternummer eingeblendet.

P05

  .... Korrektur Fühler 1 .................................. ± 10.0 K ..................................................................................................................0

P06

  .... Korrektur Fühler 2 .................................. -10,1...+10.0 K (Mit der Einstellung -10.1 ist dieser Fühler abgeschaltet,  ............0

 

 

Anzeige wechselt dann auf "oFF")

P07

  .... Alarm-Obergrenze Fühler 1 ................... -50...+300°C ...........................................................................................................+100°C

P08

  .... Alarm-Untergrenze Fühler 1 .................. -50...P07 ................................................................................................................-50°C

P09

  .... Alarm-Obergrenze Fühler 2 ................... -50...+300°C ...........................................................................................................+100°C

P10

  .... Alarm-Untergrenze Fühler 2 .................. -50...P09 ................................................................................................................-50°C

P11

  .... Alarmverzögerung ................................. 1...99 Minuten ........................................................................................................60 Minuten

P12

  .... Alarmquittierungszeit ............................. 0...99 Minuten (0=keine Alarmwiederholung nach Quittierung) .............................15 Minuten

P13

  .... Restlaufzeit Alarm/Quittierung ...............................................................................................................................................Nur Anzeige

P14

  .... Zugangscode .........................................................................................................................................................................00   

Parameters
No. 

Parameter 

Range 

Factory set 

P01

  .... Actual value sensor input 1 .................... -60,0...110,0°C (-60,0...+310,0°C mit TF 5x1) .......................................................-- 

P02

  .... Actual value sensor input 2 .................... -60,0...110,0°C (-60,0...+310,0°C mit TF 5x1) .......................................................-- 

P03

  .... Kind of connected sensors .................... 0=TF 201/°C, 1=TF 201/°F, 2=TF 202/°C, 3=TF 202/°F  .......................................0

 

 

4=TF 501/°C, 5=TF 501/°F

P04

  .... Alternating Mode .................................... 0= not alternating ...................................................................................................0

 

 

1= every 16 seconds the display changes from P01 to P02. 

In doing so, 

 

 

the parameter number appears always for a short time

P05

  .... Correction sensor 1 ............................... ± 10.0 K ..................................................................................................................0

P06

  .... Correction sensor 2 ............................... -10,1...+10.0 K (With setting to -10.1 this input is switched off,  ............................0

 

 

display changes to "oFF")

P07

  .... Alarm upper limit of sensor input 1 ........ -50...+300°C ...........................................................................................................+100

P08

  .... Alarm lower limit of sensor input 1 ......... -50...P07 ................................................................................................................-50

P09

  .... Alarm upper limit of sensor input 2 ........ -50...+300°C ...........................................................................................................+300

P10

  .... Alarm lower limit of sensor input 2 ......... -50...P09 ................................................................................................................-50

P11

  .... Alarm delay ............................................ 1...99 minutes ........................................................................................................60 minutes

P12

  .... Alarm repetition time .............................. 0...99 minutes (0 = no alarm repetition after a reset) .............................................15 minutes

P13

  .... Remaining time Alarm/Reset .................................................................................................................................................display only

P14

  .... Access Code .......................................... 88 ...........................................................................................................................00