Alarm diagrams
IT
ES
EN
EN
FR
IT
ES
9. Alarm diagrams
9.1 Alarm; Connector white
Alarm = threshold violation
- Alarm: Contact open
- Datalogger requires an external power supply for signaling
Supply, Contact input, Alarm 2
- Relays
- Switching load max. 42VAC or VDC; 500mA
Alarm = Threshold value violation or failure of external power supply
- Alarm: Contact open
- Relays
- Switching load max. 42VAC or VDC; 500mA
Alarm = Threshold value violation, failure of external power supply or cable break
- Alarm: Contact open
- Relays
- Switching load max. 42VAC or VDC; 500mA
Alarm = Threshold value violation or cable break
- Alarm: Contact open
- Datalogger does not require external power supply
- Semi-conductor contact! Use only for DC voltage (DCV)
- Switch load max. 24VDC; 200mA
9.1.1
Elpro telephone dialing device
- Alarm: Threshold violation, loss of datalogger power or cable damage
between datalogger and telephone dialing device.
- Jumper 16, see image
- Settings B-TEL 2
Set "Connection type" to "positive command"
THE REPRESENTATIONS OF THE ALARM CONTACTS CORRESPOND TO A LOGGER NOT
CONNECTED TO A POWER SUPPLY UNIT OR DURING AN ALARM!
9.2 Supply; Connector red
Alarm = Threshold value violation
- Alarm: Contact closed
- Semi-conductor contact! Use only for DC voltage (DCV)
- Signalization has its own power supply
- Switch load max. 24VDC; 200mA