5.11.7 Long PQ event special record
Most of the power quality events as specified in the
EN50160 standard occur in a very short time periods
(less than a second). If a demand to make a special
(not according to EN50160) and long record (several
seconds) exists the following definitions must be
done:
1
Activate the EN50160 mode by repeating the steps
from chapter 5.11.6.
2
Scroll to
Long Event Length
.
3
Click "Enter", the
Long Event Length
screen
appears.
Figure 5.24.
Long Event Length
4
In order to set the value in seconds (recommended is
no more than 8 seconds) use button
“F3”
or
“F4”
to
move the cursor left or right and Button
“F1”
or
“F2”
to decrease or increase the value
+
or
-
.