During  normal  operation  the  output  voltage  will  automatically  match  input 
voltage. On loss of input voltage the internal standby battery will supply the load, 
only BATT and the voltage indication will be illuminated at this time. 
The battery will continue to supply the load until either the input is restored or its 
Deep  Discharge  Protection  threshold  is  reached,  whereupon  the  UPS  will 
automatically shut down. 
 
The UPS will fully recharge from cut-off in approximately 12 – 16 hours 
Should  the  output  be  overloaded  or  become  short  circuit  the  UPS  will 
automatically disconnect the output and illuminate the PROTECT LED. 
Remove short/overload and cycle the input to reset the UPS. 
 
Note: The UPS will automatically switch off after 30s in standby mode if the load is 
<50mA 
 
Approximate backup times @12V dc: 

 
1A  

 

35mins 

0.75A 

 

70mins 

0.5A 

 

~  

120mins 

 

 

M

AINTENANCE

 

 

 

This  unit  is  intended  for  use  by  Service  Personnel  only.    There  are  NO  USER 
SERVICEABLE parts inside. 

 

There is no regular maintenance required of the UPS other than periodic testing.

 

 
 
 

 