+
Mains Power Up
1)
With no external connections made to the PSU, connect the mains input wires to the terminal block,
ensuring that the mains isolator (disconnect device) is open
. Fasten wiring in place with cable tie to
saddle.
Note: Equipment must be earthed.
2)
Apply mains input. Confirm that all LED indicators flash on briefly proving integrity of indicating circuits.
Ensure that the green Mains LED then stays illuminated and that the yellow Fault LED flashes after
approximately 3 s (indicating a disconnected battery).
3)
Disconnect the mains power.
Load Output and Remote Signalling
4)
Connect the EPS and GEN PSU Fault outputs to the appropriate inputs of control equipment if remote fault
monitoring is required.
5)
Connect the load (output) wiring as shown in Figure. 3. Cable tie to saddle provided (adjacent to exit
hole).
Figure 3 - Connections
Battery Select
Mains ON
Diagnostic LED
Fault LED
L E N
Mains
Temperature
Sensor connect
+ -
+
To Load
6)
Re-apply mains. Verify that the green Mains LED illuminates and the yellow Fault LED flashes after
approximately 3 s (disconnected battery).
7)
If connected, verify that the EPS Fault monitor shows a
closed
contact and the GEN PSU Fault monitor
shows an
open
contact.
8)
Perform a full functional test of system including full alarm condition.
9)
For 17 Ah batteries fit the link to the Battery select pins as indicated, for 7 or 2.1 Ah batteries remove link,
as shown in Figure 3.
Figure 4 – Terminal labels
Standby Battery
LOAD FUSE
2.5 Amp
BATT FUSE
2.5 Amp
+ - | + - |Temp| GEN EPS
Load | Batt |sense| Fault
10)
Mount the appropriate batteries as shown above. Where a dual box solution is used all cabling between
the two boxes should be routed to use separate case entry/exit holes from other cabling and use suitable
bushes to protect the cables
.
C
OMMISSIONING
www.acornfiresecurity.com
www.acornfiresecurity.com